R-32 (A2L)

R-32 Superheat & Subcooling Calculator

Check charge on R-32 equipment with the calculator preloaded for the pure A2L refrigerant used in ductless mini splits. Full PT chart, every grade cited to its source, and the service notes that make R-32 different: zero glide, higher head pressures, hotter discharge.

Quick answer: The target comes from the equipment maker. Where it publishes no superheat for a TXV or EEV, California Title 24 Table RA3.2-1 sets 4–25°F; subcooling is checked in cooling, at an outdoor air dry bulb of 55°F to 120°F and a return air dry bulb of at least 70°F within ±3°F of the unit’s own target. R-32 saturates at 42°F at 126 psig suction and 97°F at 312 psig liquid. It is a pure refrigerant with zero glide, so one saturation temperature works for both superheat and subcooling. Superheat = suction line temp − saturated suction temp. Subcooling = saturated liquid temp − liquid line temp.

R-32 Pressure-Temperature Chart

R-32 saturation temperature at gauge pressure. Single column, zero glide.

Swipe the table sideways to see the rest of its columns. →

R-32
Pressure (psig)Sat. Temp (°F)Publisher spread (°F)
11-40°F0
14.4-35°F0.07
18.2-30°F0
22.3-25°F0
26.8-20°F0
31.7-15°F0.05
37.1-10°F0
42.9-5°F0
49.30°F0.07
56.15°F0
63.510°F0
71.515°F0.06
8020°F0
89.225°F0
99.130°F0
109.735°F0.02
12140°F0
13345°F0
145.950°F0.04
159.555°F0.02
174.160°F0.03
189.565°F0
205.870°F0
223.275°F0.01
241.580°F0
260.985°F0
281.390°F0
302.995°F0.01
325.7100°F0
349.6105°F0.02
374.9110°F0
401.4115°F0
429.3120°F0
458.6125°F0.02
489.4130°F0.02
521.8135°F0
555.7140°F0.01
591.4145°F0
628.8150°F0

About the spread column. It is the widest gap in saturation temperature between the published tables we hold, at that pressure, on the saturation column. Across this chart the widest is 0.07°F, at 14.4 psig. Our table and 2 other published tables are compared here: 2 are separate publishers. A dash in the column: no other published table is compared at this pressure: none we hold reaches it, or this row is that table's own cell. A narrow spread means the charts agree, which is not the same as the charts being right: they are all computed from equations of state fitted to lab data, and no field measurement settles it.

Where this table comes from. Hudson Technologies R-32 PT chart, verified cell by cell.
  • Checked against Weitron, reprinted as Daikin/Goodman PM-A2LPTC-USA_04-24, within 0.1 psig on every cell it prints [separate publisher]
  • Checked against Arkema Forane, all 31 shipped cells within 0.1 psig [separate publisher]
  • Checked against CoolProp-derived tables, identical at all four anchor points [same model]

Weitron's grid steps 2 degrees F to 100, so it does not print our odd-temperature cells. Arkema's does print every one of them, including the eight from -40 to -25 F and 135 to 150 F, each within 0.1 psig of ours.

Weitron is the publisher and Daikin the reprinter, which that document's own footer states, so it is not an OEM source despite the branding. R-32 is a pure component whose saturation curve traces to one reference equation of state wherever it is printed, so these are additional publishers rather than additional models.

A separate publisher can catch a copying, edition or rounding error. A cross-check marked same model resolves to the same equation of state as the base table, so it is a consistency check rather than independent confirmation. One marked same printing prints numbers identical to another table listed here, so the two are one witness and we do not count them twice. Sources last changed 2026-10-25.

R-32 suction pressures land close to R-410A, but the high side runs noticeably higher: at 100°F condensing, R-32 reads about 326 psig where R-410A reads 317 psig. If you jump between R-410A and R-32 equipment all day, the elevated head pressure on a healthy R-32 system is normal, not a dirty condenser.


R-32 Normal Operating Pressures

R-32 suction pressures sit close to R-410A, while the high side runs noticeably higher for the same condensing temperature. The pressures at a few coil saturation temperatures, read from the PT chart above:

R-32 saturation pressures at the stated evaporator and condensing temperatures (AC mode)

Swipe the table sideways to see the rest of its columns. →

Saturation temperaturesSuction (Low)Liquid (High)
Evaporator 40°F, condensing 100°F121 psig326 psig
Evaporator 40–45°F, condensing 105–110°F121–133 psig350–375 psig
Evaporator 40–45°F, condensing 115–120°F121–133 psig401–429 psig

Which condensing temperature a unit runs at on a given day is set by the unit and its maker’s chart, not by this table. R-32's high side runs above R-410A at the same condensing temperature (about 7 psig at 90°F, 9 psig at 100°F and 13 psig at 130°F condensing), so elevated head on a healthy R-32 system is normal. Confirm the charge with superheat and subcooling, not pressure alone.


What R-32 Superheat & Subcooling Are Graded Against

TXV superheat: California Energy Commission, 2025 Reference Appendices (CEC-400-2025-010-AP), Table RA3.2-1, page RA3-19, the installer default "Superheat meets the Manufacturer's specifications or 4°F ≤ Superheat ≤ 25°F", for residential ducted split systems with a TXV or other variable metering device, installer testing: outdoor air dry bulb 55°F to 120°F, return air dry bulb at least 70°F. TXV subcooling: the maker's own target, checked within ±3°F ("Subcooling tolerance ±3°F of the manufacturer-specified target", same table) in cooling, at an outdoor air dry bulb of 55°F to 120°F and a return air dry bulb of at least 70°F. Fixed orifice: superheat against the target Table RA3.2-2 computes from indoor wet bulb and outdoor dry bulb, within ±5°F ("Superheat tolerance ±5°F of the specified target", Table RA3.2-1); subcooling only against the maker's own target with the tolerance the maker prints beside it (Lennox 13ACC Installation Instructions (form 504726), page 14, Table 6: "Liquid Subcooling [± 1°F (.6°C)]"), otherwise not graded. Refrigeration fluids: the superheat is shown and not graded, on a TXV or a fixed orifice, because these figures are residential comfort-cooling figures. Where the equipment maker prints its own figure, it governs.

Swipe the table sideways to see the rest of its columns. →

Metering deviceSuperheat graded againstSubcooling graded againstCharging method
TXV4–25°Fmaker's target ±3°FCharge by subcooling; the TXV holds superheat
Fixed orifice (piston)RA3.2-2 target ±5°Fmaker's target and printed tolerance, else not gradedCharge by superheat against its target; where the maker sets the charge by subcooling, by its target and tolerance

On an inverter mini split, the figures above are not a charging method. Compressor speed changes both pressures as it runs, so use the manufacturer test mode and the service manual tables, and charge by weight.


Where You Will See R-32

R-32 (difluoromethane) is a pure single-component A2L refrigerant with a GWP of 675. It is used across mini splits and multi-zone systems from Daikin, Mitsubishi Electric, Fujitsu, LG, and others. Some ducted and side-discharge equipment uses it as well, while ducted lines such as Carrier's and Trane's went to R-454B.

Because R-32 is a pure compound, it has zero temperature glide: it boils and condenses at a single temperature for a given pressure. That makes PT work simple. It also means vapor charging cannot fractionate anything, one of the few refrigerants left where topping off from the vapor port is technically harmless (still follow the manufacturer procedure).

R-32 Charging Notes

The two field realities that separate R-32 from R-410A: discharge temperature and charge criticality. R-32 compresses hotter at comparable conditions, so manufacturers lean on injection circuits and inverter limits to protect the compressor. A slightly overcharged or airflow-starved R-32 unit hits discharge protection faster than R-410A equipment would, which is worth remembering when a unit derates or trips on hot afternoons.

Charge criticality comes from the equipment type. Mini splits hold small, precisely specified charges: factory charge plus an adder per foot of line set beyond the base length, both printed on the nameplate. Superheat and subcooling verify the result and diagnose faults, but the charging method is the scale. When history on a system is unknown, recover, pull a proper vacuum, and weigh the charge back in rather than chasing numbers by feel.

A2L handling applies just like R-454B: A2L-rated recovery equipment and leak detectors, no open flame on a charged circuit, ventilation in tight spaces, and keep any factory refrigerant-leak sensors functional after service.


Worked Example: R-32 System Check in Test Mode

An R-32 multi-zone system running the manufacturer forced-cooling test mode, with gauge access on both service ports. Field readings: suction pressure 121 psig, suction line temperature 49°F, liquid pressure 312 psig, liquid line temperature 88°F.

Saturated suction temp at 121 psig = 40°F

Superheat = 49°F − 40°F = 9°F

Saturated liquid temp at 312 psig = 97°F

Subcooling = 97°F − 88°F = 9°F

Diagnosis: Superheat 9°F and subcooling 9°F are checked against the service manual’s test-mode values for these conditions, not against Title 24’s 4–25°F TXV default: that default is for residential ducted split systems with a TXV or other variable metering device, installer testing: outdoor air dry bulb 55°F to 120°F, return air dry bulb at least 70°F, and this is a multi-zone system. Note the higher head pressure than an R-410A tech expects: 312 psig at only 97°F condensing is normal for R-32.


R-32 Charging FAQs

What are normal operating pressures for R-32?

Read them off the PT chart at the coil temperatures: a 40 to 45F evaporator is 121 to 133 psig on the suction (low) side, and 100 to 120F condensing is 326 to 429 psig on the liquid (high) side. The suction stays near the evaporator's pressure while the high side climbs with the condensing temperature, which the outdoor air, the condenser and the load set; the maker's chart for the unit says what it should be. R-32 suction is close to R-410A, but its head runs higher at the same condensing temperature: about 7 psig at 90F, 9 psig at 100F and 13 psig at 130F condensing.

What are R-32 running pressures on a 90 degree day?

The outdoor temperature alone does not set them: the high side follows the condensing temperature, and how far that sits above a 90F day depends on the unit, its condenser airflow and the indoor load, so the maker's charging chart or service manual table for the unit is the figure to read. For a sense of scale, at 105 to 110F condensing R-32 reads 350 to 375 psig liquid, and a 40 to 45F evaporator reads 121 to 133 psig suction. The elevated head compared with R-410A is normal for R-32, not a sign of a dirty condenser or overcharge. Verify the charge with superheat and subcooling rather than pressure alone.

What should R-32 suction and head pressure be?

Suction (low side) should sit near the saturation pressure for your evaporator temperature, 121 to 133 psig for a 40 to 45F coil. Head (liquid, high side) should sit near the saturation pressure for the condensing temperature, which rises with the outdoor air; it reads 326 psig at 100F condensing up to 429 psig at 120F condensing. R-32 head reads above R-410A at the same condensing temperature (about 7 psig at 90F, 9 psig at 100F and 13 psig at 130F condensing), so do not condemn a system as overcharged just because the high side looks high on an R-410A mental baseline.

What is normal superheat for R-32?

With a TXV or EEV the target is the equipment maker's; where the maker publishes none, California Title 24 Table RA3.2-1 sets 4-25°F for residential ducted split systems with a TXV or other variable metering device, installer testing: outdoor air dry bulb 55°F to 120°F, return air dry bulb at least 70°F. With a fixed orifice, use the manufacturer charging chart, which depends on outdoor ambient and indoor wet bulb (Title 24 Table RA3.2-2 computes the same kind of target, checked within ±5°F). On inverter-driven mini splits, superheat floats with compressor speed, so check it in the manufacturer's forced-run or test mode and treat the installation manual value as the target.

Is R-32 the same as R-410A?

No, but they are related. R-410A is a 50/50 blend of R-32 and R-125; R-32 by itself is a pure single-component refrigerant. R-32 has a GWP of 675 versus 2,088 for R-410A, runs similar suction pressures, noticeably higher liquid pressures, and hotter compressor discharge temperatures. They are not interchangeable in equipment.

Can I put R-32 in an R-410A system?

No. R-410A equipment is not listed for flammable (A2L) refrigerants and lacks the leak detection and electrical design R-32 requires. Discharge temperatures also run hotter on R-32, which the R-410A compressor was not designed around. Service R-410A systems with R-410A.

Can I use R-32 gauges on R-454B?

Not for saturation readings. R-32 and R-454B have different pressure-temperature curves: at 100°F saturated, R-32 reads about 326 psig while R-454B reads about 301 psig (bubble). Reading a 454B system against an R-32 scale skews every superheat and subcooling number, and R-454B has ~2°F of glide that R-32 does not. Use the correct PT scale on your probes or select the actual refrigerant in this calculator.

Do I charge R-32 as liquid or vapor?

Either works without fractionation because R-32 is a pure compound, not a blend. Liquid charging is still faster and is what most manufacturers specify; throttle liquid slowly into the suction side so it flashes before reaching the compressor. Follow the equipment manual, and remember all handling must follow A2L practice.

Why are R-32 discharge temperatures so high?

R-32 has a higher heat of compression than R-410A, so compressor discharge runs hotter at comparable conditions. Manufacturers manage this with vapor or liquid injection and discharge temperature limits in the inverter logic. For the tech it means discharge line temperature is a useful health check on R-32 equipment, and overcharging or restricted airflow shows up as discharge overheat trips sooner than it would on R-410A.

How do I check the charge on an R-32 mini split?

Weigh-in is the primary method: mini splits are critically charged, and the nameplate lists the factory charge plus an ounces-per-foot adder for line sets beyond the base length. Superheat and subcooling are verification and diagnostic tools, not the charging method. Run the unit in the manufacturer's test mode, compare readings to the service manual table for the current conditions, and if the charge is in doubt, recover, evacuate, and weigh it back in.


R-32 Reference & Comparisons

Other Refrigerants & Related Tools

R-454B Superheat & Subcooling Calculator

The A2L replacement for R-410A in new ducted systems. PT chart, cited charge checks, and A2L charging notes.

R-410A Superheat & Subcooling Calculator

The dominant installed base from 2010 to 2025. PT chart and cited charge checks.

R-22 Superheat & Subcooling Calculator

Legacy HCFC: serviced with recycled, reclaimed or previously produced R-22 since 2020. PT chart and cited charge checks for servicing older systems.

R-134a Superheat & Subcooling Calculator

Medium-temp refrigeration, chillers, and automotive AC. PT chart and cited reference figures.

All-Refrigerant Calculator

The full calculator with 10+ refrigerants including R-407C with glide handling, plus the four-quadrant diagnostic guide.

Target Superheat Calculator

Charging a fixed-orifice (piston) system? Set the charge by target superheat from indoor wet-bulb and outdoor dry-bulb, compared to your measured superheat.

Normal Superheat & Subcooling Values

What each reading is graded against, by metering device, each figure cited, with what a high or low reading means. R-410A, R-454B, R-32, R-22, R-134a, and R-407C in one reference.

How to Calculate Superheat & Subcooling

The formulas, the step-by-step field method, and worked examples for R-410A and R-22. The math behind the calculator.

Printable Superheat & Subcooling Chart

What each reading is graded against, with its source, plus PT charts for R-410A, R-454B, and R-22, formatted to print or save as a PDF for the truck.

Subcooling on a Heat Pump

Where to measure on a heat pump in each mode, each maker's own heating-mode charging rule, and when the cooling-mode subcooling number still applies.

A2L Charge Limit Calculator

Maximum A2L charge for a room, or minimum room area for a charge, per UL 60335-2-40 and ASHRAE 15.2. Covers R-454B, R-32, and 6 more refrigerants.

EPA Refrigerant Leak Rate Calculator

Topping off a covered 15+ lb appliance triggers a leak rate calculation under 40 CFR 84.106 as of January 1, 2026. Residential and light commercial air conditioning and heat pumps are excluded by 84.106(a)(3)(ii), so on most split systems the rate is informational. Run the EPA math and check the thresholds.

BTU / HVAC Load Calculator

A house's heating and cooling loads by ACCA Manual J at your ZIP code's weather station, with the size Manual S points to.

Mini split sized by guesswork? Run the load.

Ductless heads get oversized constantly, and an oversized inverter unit short-cycles at minimum capacity. Check the house's Manual J load at your ZIP code's weather station first.