R-32 (A2L)
R-32 Superheat & Subcooling Calculator
Check charge on R-32 equipment with the calculator preloaded for the pure A2L refrigerant behind most ductless mini splits. Full PT chart, charging targets, and the service notes that make R-32 different: zero glide, higher head pressures, hotter discharge.
R-32 Pressure-Temperature Chart
| Pressure (psig) | Sat. Temp (°F) | Publisher spread (°F) |
|---|---|---|
| 26.8 | -20°F | 0 |
| 37.1 | -10°F | 0 |
| 49.3 | 0°F | 0.07 |
| 63.5 | 10°F | 0 |
| 71.5 | 15°F | 0.06 |
| 80 | 20°F | 0 |
| 89.2 | 25°F | 0 |
| 99.1 | 30°F | 0 |
| 109.7 | 35°F | 0.02 |
| 121 | 40°F | 0 |
| 133 | 45°F | 0 |
| 145.9 | 50°F | 0.04 |
| 159.5 | 55°F | 0.02 |
| 174.1 | 60°F | 0.03 |
| 189.5 | 65°F | 0 |
| 205.8 | 70°F | 0 |
| 223.2 | 75°F | 0.01 |
| 241.5 | 80°F | 0 |
| 260.9 | 85°F | 0 |
| 281.3 | 90°F | 0 |
| 302.9 | 95°F | 0.01 |
| 325.7 | 100°F | 0 |
| 349.6 | 105°F | 0.02 |
| 374.9 | 110°F | 0 |
| 401.4 | 115°F | 0 |
| 429.3 | 120°F | 0 |
| 458.6 | 125°F | 0.02 |
| 489.4 | 130°F | 0.02 |
About the spread column. It is the widest gap in saturation temperature between the published tables we hold, at that pressure, on the saturation column. Across this chart the widest is 0.07°F, at 49.3 psig. Our table and 2 other published tables are compared here: 2 are separate publishers. A narrow spread means the charts agree, which is not the same as the charts being right: they are all computed from equations of state fitted to lab data, and no field measurement settles it.
- Checked against Weitron, reprinted as Daikin/Goodman PM-A2LPTC-USA_04-24, within 0.1 psig on every cell it prints [separate publisher]
- Checked against Arkema Forane, all 28 shipped cells within 0.1 psig [separate publisher]
- Checked against CoolProp-derived tables, identical at all four anchor points [same model]
Weitron's grid steps 2 degrees F to 100, so it does not print our odd-temperature cells. Arkema's does print every one of them.
Weitron is the publisher and Daikin the reprinter, which that document's own footer states, so it is not an OEM source despite the branding. R-32 is a pure component whose saturation curve traces to one reference equation of state wherever it is printed, so these are additional publishers rather than additional models.
A separate publisher can catch a transcription, edition or rounding error. A cross-check marked same model resolves to the same equation of state as the base table, so it is a consistency check rather than independent confirmation. One marked same printing prints numbers identical to another table listed here, so the two are one witness and we do not count them twice. Sources last re-verified 2026-08-05.
R-32 suction pressures land close to R-410A, but the high side runs noticeably higher: at 100°F condensing, R-32 reads about 326 psig where R-410A reads 317 psig. If you jump between R-410A and R-32 equipment all day, the elevated head pressure on a healthy R-32 system is normal, not a dirty condenser.
R-32 Normal Operating Pressures
R-32 suction pressures sit close to R-410A, while the high side runs noticeably higher for the same condensing temperature. On a properly charged R-32 system in cooling, expect roughly these running pressures, read from the PT chart above:
| Outdoor Conditions | Suction (Low) | Liquid (High) |
|---|---|---|
| Mild day, ~75°F | ~121 psig | ~326 psig |
| Warm day, ~85–90°F | ~121–133 psig | ~350–375 psig |
| Hot day, ~95°F+ | ~121–133 psig | ~401–429 psig |
Suction assumes a 40–45°F evaporator saturation; liquid assumes condensing about 15–25°F above ambient. R-32's high side runs about 9 to 13 psig above R-410A at the same condensing temperature, so elevated head on a healthy R-32 system is normal. Confirm the charge with superheat and subcooling, not pressure alone.
R-32 Target Superheat & Subcooling
| Metering device | Target superheat | Target subcooling | Charging method |
|---|---|---|---|
| TXV | 8–15°F | 8–14°F | Charge by subcooling; the TXV holds superheat |
| Fixed orifice (piston) | 5–20°F | 4–10°F | Charge by superheat from the manufacturer charging chart |
On inverter mini splits, these generic ranges are a sanity check, not a charging method. Compressor speed changes both pressures continuously, so always use the manufacturer test mode and the service manual tables, and charge by weight.
Where You Will See R-32
R-32 (difluoromethane) is a pure single-component A2L refrigerant with a GWP of 675. It has dominated ductless equipment worldwide for a decade, and in the US it is now standard across mini splits and multi-zone systems from Daikin, Mitsubishi Electric, Fujitsu, LG, and others. Some ducted and side-discharge equipment uses it as well, though most US ducted lines went to R-454B. If you service ductless, you service R-32.
Because R-32 is a pure compound, it has zero temperature glide: it boils and condenses at a single temperature for a given pressure. That makes PT work simple. It also means vapor charging cannot fractionate anything, one of the few refrigerants left where topping off from the vapor port is technically harmless (still follow the manufacturer procedure).
R-32 Charging Notes
The two field realities that separate R-32 from R-410A: discharge temperature and charge criticality. R-32 compresses hotter, roughly 15–30°F higher discharge temperature at comparable conditions, so manufacturers lean on injection circuits and inverter limits to protect the compressor. A slightly overcharged or airflow-starved R-32 unit hits discharge protection faster than R-410A equipment would, which is worth remembering when a unit derates or trips on hot afternoons.
Charge criticality comes from the equipment type. Mini splits hold small, precisely specified charges: factory charge plus an adder per foot of line set beyond the base length, both printed on the nameplate. Superheat and subcooling verify the result and diagnose faults, but the charging method is the scale. When history on a system is unknown, recover, pull a proper vacuum, and weigh the charge back in rather than chasing numbers by feel.
A2L handling applies just like R-454B: A2L-rated recovery equipment and leak detectors, no open flame on a charged circuit, ventilation in tight spaces, and keep any factory refrigerant-leak sensors functional after service.
Worked Example: R-32 System Check in Test Mode
An R-32 multi-zone system running the manufacturer forced-cooling test mode, with gauge access on both service ports. Field readings: suction pressure 121 psig, suction line temperature 49°F, liquid pressure 312 psig, liquid line temperature 88°F.
Saturated suction temp at 121 psig = 40°F
Superheat = 49°F − 40°F = 9°F
Saturated liquid temp at 312 psig = 97°F
Subcooling = 97°F − 88°F = 9°F
Diagnosis: Superheat 9°F and subcooling 9°F both land inside the 8–15°F and 8–14°F targets. The charge checks out against the service manual values for these conditions. Note the higher head pressure than an R-410A tech expects: 312 psig at only 97°F condensing is normal for R-32.
R-32 Charging FAQs
What are normal operating pressures for R-32?
A properly charged R-32 air conditioner typically runs about 121 to 133 psig on the suction (low) side, matching a 40 to 45F evaporator, and 326 to 429 psig on the liquid (high) side depending on outdoor temperature. On a mild 75F day expect roughly 121 psig / 326 psig; on a hot 95F-plus day the high side climbs to about 401 to 429 psig while suction stays near 121 to 133 psig. R-32 suction is close to R-410A, but its head runs about 9 to 13 psig higher at the same condensing temperature.
What are R-32 running pressures on a 90 degree day?
On about a 90F day, a healthy R-32 system in cooling runs roughly 121 to 133 psig suction (40 to 45F evaporator) and 350 to 375 psig liquid (condensing around 105 to 110F, or 15 to 20F above ambient). The elevated head compared with R-410A is normal for R-32, not a sign of a dirty condenser or overcharge. Verify the charge with superheat and subcooling rather than pressure alone.
What should R-32 suction and head pressure be?
Suction (low side) should sit near the saturation pressure for your evaporator temperature, about 121 to 133 psig for a 40 to 45F coil. Head (liquid, high side) should sit near the saturation pressure for a condensing temperature 15 to 25F above the outdoor air, which lands around 326 psig at 100F condensing up to about 429 psig at 120F condensing. R-32 head reads roughly 9 to 13 psig above R-410A at the same condensing temperature, so do not condemn a system as overcharged just because the high side looks high on an R-410A mental baseline.
What is normal superheat for R-32?
With a TXV or EEV, target superheat for R-32 is 8-15°F. With a fixed orifice, use the manufacturer charging chart (typically 5-20°F depending on outdoor ambient and indoor wet bulb). On inverter-driven mini splits, superheat floats with compressor speed, so check it in the manufacturer's forced-run or test mode and treat the installation manual value as the target.
Is R-32 the same as R-410A?
No, but they are related. R-410A is a 50/50 blend of R-32 and R-125; R-32 by itself is a pure single-component refrigerant. R-32 has a GWP of 675 versus 2,088 for R-410A, runs similar suction pressures, noticeably higher liquid pressures, and hotter compressor discharge temperatures. They are not interchangeable in equipment.
Can I put R-32 in an R-410A system?
No. R-410A equipment is not listed for flammable (A2L) refrigerants and lacks the leak detection and electrical design R-32 requires. Discharge temperatures also run hotter on R-32, which the R-410A compressor was not designed around. Service R-410A systems with R-410A.
Can I use R-32 gauges on R-454B?
Not for saturation readings. R-32 and R-454B have different pressure-temperature curves: at 100°F saturated, R-32 reads about 326 psig while R-454B reads about 301 psig (bubble). Reading a 454B system against an R-32 scale skews every superheat and subcooling number, and R-454B has ~2°F of glide that R-32 does not. Use the correct PT scale on your probes or select the actual refrigerant in this calculator.
Do I charge R-32 as liquid or vapor?
Either works without fractionation because R-32 is a pure compound, not a blend. Liquid charging is still faster and is what most manufacturers specify; throttle liquid slowly into the suction side so it flashes before reaching the compressor. Follow the equipment manual, and remember all handling must follow A2L practice.
Why are R-32 discharge temperatures so high?
R-32 has a higher heat of compression than R-410A, so compressor discharge runs roughly 15-30°F hotter at comparable conditions. Manufacturers manage this with vapor or liquid injection and discharge temperature limits in the inverter logic. For the tech it means discharge line temperature is a useful health check on R-32 equipment, and overcharging or restricted airflow shows up as discharge overheat trips sooner than it would on R-410A.
How do I check the charge on an R-32 mini split?
Weigh-in is the primary method: mini splits are critically charged, and the nameplate lists the factory charge plus an ounces-per-foot adder for line sets beyond the base length. Superheat and subcooling are verification and diagnostic tools, not the charging method. Run the unit in the manufacturer's test mode, compare readings to the service manual table for the current conditions, and if the charge is in doubt, recover, evacuate, and weigh it back in.
R-32 Reference & Comparisons
Other Refrigerants & Related Tools
R-454B Superheat & Subcooling Calculator
The A2L replacement for R-410A in new ducted systems. PT chart, TXV targets, and A2L charging notes.
R-410A Superheat & Subcooling Calculator
The dominant installed base from 2010 to 2025. PT chart and TXV charging targets.
R-22 Superheat & Subcooling Calculator
Legacy HCFC on reclaimed supply only. PT chart and targets for servicing older systems.
R-134a Superheat & Subcooling Calculator
Medium-temp refrigeration, chillers, and automotive AC. PT chart and charging targets.
All-Refrigerant Calculator
The full calculator with 10+ refrigerants including R-407C with glide handling, plus the four-quadrant diagnostic guide.
Target Superheat Calculator
Charging a fixed-orifice (piston) system? Set the charge by target superheat from indoor wet-bulb and outdoor dry-bulb, compared to your measured superheat.
Normal Superheat & Subcooling Values
The target numbers by refrigerant and metering device, with what a high or low reading means. R-410A, R-454B, R-32, R-22, R-134a, and R-407C in one reference.
How to Calculate Superheat & Subcooling
The formulas, the step-by-step field method, and worked examples for R-410A and R-22. The math behind the calculator.
Printable Superheat & Subcooling Chart
Target ranges by refrigerant plus PT charts for R-410A, R-454B, and R-22, formatted to print or save as a PDF for the truck.
Subcooling on a Heat Pump
Why heat pumps have no subcooling target in heating mode, how to charge by weigh-in, and when the cooling-mode subcooling number still applies.
A2L Charge Limit Calculator
Maximum A2L charge for a room, or minimum room area for a charge, per UL 60335-2-40 and ASHRAE 15.2. Covers R-454B, R-32, and 6 more refrigerants.
EPA Refrigerant Leak Rate Calculator
Topping off a covered 15+ lb appliance triggers a leak rate calculation under 40 CFR 84.106 as of January 1, 2026. Residential and light commercial air conditioning and heat pumps are excluded by 84.106(a)(3)(ii), so on most split systems the rate is informational. Run the EPA math and check the thresholds.
BTU / HVAC Load Calculator
Size the system by climate zone, insulation, windows, and duct location with automatic tonnage recommendations.
Mini split sized by guesswork? Run the load.
Ductless heads get oversized constantly, and an oversized inverter unit short-cycles at minimum capacity. Check the room load by climate zone, insulation, and windows first.