120V Induction Range Circuit

Impulse Cooktop: Circuit & the Shared-Circuit Verdict

The circuit the Impulse Cooktop needs, sized from the 15A wall draw the manufacturer states (never the induction burner kW), with the NEC shared-circuit verdict.

Quick answer: the Impulse Cooktop draws 15A from the wall at 120V, so a dedicated circuit is a 15A breaker on #14 copper with a #14 copper ground. On a shared 15A general-purpose circuit it needs a dedicated circuit (it cannot share a general-purpose 15A or 20A circuit) (NEC 210.23(B)(2), cap 7.5A).

Circuit Spec

Circuit specification for the Impulse Cooktop, sized from the stated wall draw

Swipe the table sideways to see the rest of its columns. →

Plug / voltageNEMA 5-15P (120V or 240V)
Wall / charge draw (manufacturer-stated)15 A
Share a general-purpose 15A circuit?Needs a dedicated circuit
Share a general-purpose 20A circuit?Needs a dedicated circuit
Dedicated circuit (recharge under 3 h)15A / #14 Cu, #14 Cu ground
Dedicated circuit (continuous, 3 h+ recharge)20A / #12 Cu, #12 Cu ground (18.75A design)
Service-load contribution~1.44 kVA (vs 8 kW for a 240V range of 12 kW or less)
Battery~3 kWh
Safety listingUL 858

The wall draw is the manufacturer-stated value; the breaker, wire, ground, verdict, and service-load figure derive from it. The rating plate on your unit governs.

Models

Representative models in this line: Impulse Cooktop 30", Impulse Cooktop 36". The circuit spec above applies across the line as published by Impulse; confirm against the rating plate on the specific unit.

Can It Share a Circuit?

Needs a dedicated circuit on a 15A circuit. 15 A exceeds the 7.5 A cap for a general-purpose / multi-outlet 15 A circuit (15 A x 50% = 7.5 A), so it is NOT permitted to share a 15 A circuit; it needs a dedicated individual branch circuit.

A drop-in cooktop is FIXED (fastened or otherwise secured at a specific location, the NEC Art. 100 definition), so on a general-purpose / multi-outlet circuit the stricter NEC 210.23(B)(2) caps its rating at 50% of the branch: 7.5A on a 15A circuit, 10A on a 20A. The cord-and-plug connection does not change that; “fastened in place” is about the mounting, not the plug. On a 20A circuit: 15 A exceeds the 10 A cap for a general-purpose / multi-outlet 20 A circuit (20 A x 50% = 10 A), so it is NOT permitted to share a 20 A circuit; it needs a dedicated individual branch circuit.

It needs its own circuit. Can your panel take it?

At its full 15A wall draw the Impulse Cooktop needs a dedicated circuit; as a fixed-in-place unit it cannot share even a 20A general-purpose circuit. Adding a circuit raises the panel question: does the service have room and spare capacity for it?

Source

Circuit data read from the manufacturer: Impulse Cooktop specification, accessed 2026-07-11. Sourced from the manufacturer's product page rather than a spec sheet PDF.

The Impulse Cooktop (Impulse Labs) is a four-burner 30/36-inch cooktop with a 3 kWh LFP battery, certified to UL 858. It runs on 120V/15A (NEMA 5-15P) OR a 240V circuit; the burners deliver up to 10,000 watts of peak power per burner from the battery, but the wall side is a 15A branch. Impulse's own pages do not print a continuous wall-draw figure below the 15A breaker rating, so none is invented here.

The documents behind these figures, and the code sections this page cites, are named in the source receipt.


Frequently Asked Questions

Can the Impulse Cooktop share a circuit?

On a general-purpose / multi-outlet circuit, 15 A exceeds the 7.5 A cap for a general-purpose / multi-outlet 15 A circuit (15 A x 50% = 7.5 A), so it is NOT permitted to share a 15 A circuit; it needs a dedicated individual branch circuit. On a 20A circuit: 15 A exceeds the 10 A cap for a general-purpose / multi-outlet 20 A circuit (20 A x 50% = 10 A), so it is NOT permitted to share a 20 A circuit; it needs a dedicated individual branch circuit. The rule: NEC 210.23(B)(2) (utilization equipment fastened in place, 50% of a general-purpose / multi-outlet branch circuit); a drop-in cooktop is a fixed appliance (NEC Art. 100), so the 50% cap governs, not the 80% (B)(1) not-fastened rule.

What breaker and wire does the Impulse Cooktop need?

Size it from the 15A wall / charge draw off the rating plate, never the induction burner kW (those peaks come from the battery). On a dedicated individual branch circuit it takes a 15A breaker on #14 copper with a #14 copper equipment ground. If the battery recharge runs 3 hours or more it is a continuous load and the circuit is sized to 125% (NEC 210.20(A)): 15 x 1.25 = 18.75A, a 20A breaker on #12 copper. GFCI: NEC 2023 210.8(D) requires GFCI protection for the branch circuit or outlet supplying a 120V induction range or drop-in cooktop (210.8(D)(8) "Electric ranges", 210.8(D)(10) "Counter-mounted cooking units") rated 150 volts or less to ground and 60 amperes or less, hardwired or plugged in, wherever it is installed; which edition applies is the one your jurisdiction has adopted.

Does the Impulse Cooktop need a dedicated circuit?

At its full 15A wall draw it exceeds the 7.5A shared-circuit cap for a 15A circuit (fastened-in-place 50%, NEC 210.23(B)(2)), so it needs a dedicated individual branch circuit (it cannot share a 20A circuit either, 10A cap). Impulse states a 15A breaker minimum for both the 120V and 240V use cases and that the panel does not need to be upgraded. It does not state 'dedicated'; it plugs directly into an existing 120V outlet. As a drop-in (fixed / fastened-in-place) cooktop its shared-circuit rating is capped by NEC 210.23(B)(2) at 50% (7.5A on a 15A circuit, 10A on a 20A), so its 15A draw exceeds the shared cap on both a 15A and a 20A general-purpose circuit: it wants a dedicated branch circuit to itself, not a shared one.

How much does the Impulse Cooktop add to my service load?

About 1.8 kVA (15A x 120V), just over the 1-3/4 kW Table 220.55 threshold, so Note 3 applies the Column A single-unit 80% demand factor: 1.8 x 0.80 = 1.44 kW. That is far below the 8 kW Column-C demand a conventional 240V range rated 12 kW or less gets, which is why it can fit a service that could not take another 240V range, where a load calculation shows the room.


Check the Circuit

Confirm against your unit's rating plate: enter the wall / charge draw and the circuit rating to get the shared-circuit verdict and the dedicated wire and breaker.


Other 120V Induction Ranges

Related Tools