120V Induction Range Circuit
Electra Induction Stove: Circuit & the Shared-Circuit Verdict
The circuit the Electra Induction Stove needs, sized from the 15A wall draw the manufacturer states (never the induction burner kW), with the NEC shared-circuit verdict.
Circuit Spec
| Plug / voltage | Standard 120V outlet (120V) |
| Wall / charge draw (manufacturer-stated) | 15 A |
| Share a general-purpose 15A circuit? | Needs a 20A or dedicated circuit |
| Share a general-purpose 20A circuit? | Can share a circuit |
| Dedicated circuit (recharge under 3 h) | 15A / #14 Cu |
| Dedicated circuit (continuous, 3 h+ recharge) | 20A / #12 Cu (18.75A design) |
| Equipment ground | #14 Cu |
| Service-load contribution | ~1.44 kVA (vs 8 kW for a 240V range) |
| Battery | ~5 kWh |
| Safety listing | Not printed by the manufacturer |
The wall draw is the manufacturer-stated value; the breaker, wire, ground, verdict, and service-load figure derive from it. The rating plate on your unit governs.
Models
Representative models in this line: The Electra Induction Stove. The circuit spec above applies across the line as published by Electra; confirm against the rating plate on the specific unit.
Can It Share a Circuit?
A freestanding range is cord-and-plug connected and not fastened in place, so on a general-purpose / multi-outlet circuit NEC 210.23(B)(1) caps its rating at 80% of the branch: 12A on a 15A circuit, 16A on a 20A (companion Table 210.21(B)(2)). On a 20A circuit: 15 A is within the 16 A cap for a general-purpose / multi-outlet 20 A circuit (20 A x 80% = 16 A), so it may share that circuit. Electra's Breaker Saver dials the wall draw down to 12A, which sits at the 12A cap, so a dialed-down unit fits a shared 15A circuit.
Source
Circuit data transcribed from the manufacturer: Electra Induction Stove specification, accessed 2026-07-11. Sourced from the manufacturer's product page rather than a spec sheet PDF.
The Electra Induction Stove (ships April 2026, $3,999) is a freestanding range that plugs into a standard 120V outlet and states 120V, 15A. Its 5 kWh battery feeds the burners (1800/1800/900/900 W) and 4900 W oven, all far above the ~12A/1440W wall cap. Electra does not print a NEMA plug type, so none is listed here.
Frequently Asked Questions
Can the Electra Induction Stove share a circuit?
On a general-purpose / multi-outlet circuit, 15 A exceeds the 12 A cap for a general-purpose / multi-outlet 15 A circuit (15 A x 80% = 12 A), so it is NOT permitted to share a 15 A circuit; it needs a 20 A circuit or a dedicated individual branch circuit. On a 20A circuit: 15 A is within the 16 A cap for a general-purpose / multi-outlet 20 A circuit (20 A x 80% = 16 A), so it may share that circuit. The rule: NEC 210.23(B)(1) (cord-and-plug equipment not fastened in place, 80% of a general-purpose / multi-outlet branch circuit) with the companion receptacle limit of NEC 210.21(B)(2) and Table 210.21(B)(2). Electra's Breaker Saver can dial the wall draw down to 12A, which sits exactly at the 12A cap, so a dialed-down unit fits a shared 15A circuit.
What breaker and wire does the Electra Induction Stove need?
Size it from the 15A wall / charge draw off the rating plate, never the induction burner kW (those peaks come from the battery). On a dedicated individual branch circuit it takes a 15A breaker on #14 copper with a #14 copper equipment ground. If the battery recharge runs 3 hours or more it is a continuous load and the circuit is sized to 125% (NEC 210.20(A)): 15 x 1.25 = 18.75A, a 20A breaker on #12 copper.
Does the Electra Induction Stove need a dedicated circuit?
At its full 15A wall draw it exceeds the 12A cord-and-plug cap for a shared 15A circuit, so it needs a 20A circuit (16A cap) or a dedicated individual branch circuit. Electra plugs into a standard 120V outlet (no renovation required) and states 120V, 15A. It imposes no dedicated-circuit requirement and adds explicit shared-circuit support: the Breaker Saver feature dials the wall draw between 2 and 12 amps to avoid tripping the breaker, the strongest adjustable wall-draw bound on this roster.
How much does the Electra Induction Stove add to my service load?
About 1.8 kVA (15A x 120V), just over the 1-3/4 kW Table 220.55 threshold, so Note 3 applies the Column A single-unit 80% demand factor: 1.8 x 0.80 = 1.44 kW. That is far below the 8 kW Column-C demand a conventional 240V range gets, which is why it fits a service that could not take another 240V range.
Check the Circuit
Confirm against your unit's rating plate: enter the wall / charge draw and the circuit rating to get the shared-circuit verdict and the dedicated wire and breaker.
Other 120V Induction Ranges
Copper Charlie Induction Range
12A wall draw. Shares at the cap (no headroom) on a shared 15A.
Impulse Cooktop
15A wall draw. Needs a 20A or dedicated circuit on a shared 15A.
Breaker & Wire Chart
Every unit on one table: wall draw, shared verdict, dedicated breaker and wire.
120V vs 240V
The plug-in class next to a conventional 240V range: circuit, wiring, and recovery.
Related Tools
What Size Breaker Do I Need
Breaker sizes for common loads, worked from the nameplate out.
Wire Size for Appliances
Standard circuit and wire per appliance, including the conventional electric range.
Appliance Amps
Typical running amps for common household appliances and the circuit each needs.
Load Calculator (NEC 220)
Can the panel handle it? NEC 220.82 sizing and the 220.87 existing-load check.