120V Induction Range Circuit

Electra Induction Stove: Circuit & the Shared-Circuit Verdict

The circuit the Electra Induction Stove needs, sized from the 15A wall draw the manufacturer states (never the induction burner kW), with the NEC shared-circuit verdict.

Quick answer: the Electra Induction Stove draws 15A from the wall at 120V, so a dedicated circuit is a 15A breaker on #14 copper with a #14 copper ground. On a shared 15A general-purpose circuit it needs a 20A or dedicated circuit, not a shared 15A one (NEC 210.23(B)(1), cap 12A).

Circuit Spec

Circuit specification for the Electra Induction Stove, sized from the stated wall draw

Swipe the table sideways to see the rest of its columns. →

Plug / voltageStandard 120V outlet (120V)
Wall / charge draw (manufacturer-stated)15 A
Share a general-purpose 15A circuit?Needs a 20A or dedicated circuit
Share a general-purpose 20A circuit?Can share a circuit
Dedicated circuit (recharge under 3 h)15A / #14 Cu, #14 Cu ground
Dedicated circuit (continuous, 3 h+ recharge)20A / #12 Cu, #12 Cu ground (18.75A design)
Service-load contribution~1.44 kVA (vs 8 kW for a 240V range of 12 kW or less)
Battery~5 kWh
Safety listingNot printed by the manufacturer

The wall draw is the manufacturer-stated value; the breaker, wire, ground, verdict, and service-load figure derive from it. The rating plate on your unit governs.

Models

Representative models in this line: The Electra Induction Stove. The circuit spec above applies across the line as published by Electra; confirm against the rating plate on the specific unit.

Can It Share a Circuit?

Needs a 20A or dedicated circuit on a 15A circuit. 15 A exceeds the 12 A cap for a general-purpose / multi-outlet 15 A circuit (15 A x 80% = 12 A), so it is NOT permitted to share a 15 A circuit; it needs a 20 A circuit or a dedicated individual branch circuit.

A freestanding range is cord-and-plug connected and not fastened in place, so on a general-purpose / multi-outlet circuit NEC 210.23(B)(1) caps its rating at 80% of the branch: 12A on a 15A circuit, 16A on a 20A (companion Table 210.21(B)(2)). On a 20A circuit: 15 A is within the 16 A cap for a general-purpose / multi-outlet 20 A circuit (20 A x 80% = 16 A), so it may share that circuit. Electra's Breaker Saver dials the wall draw down to 12A, which sits at the 12A cap, so a dialed-down unit fits a shared 15A circuit.

It needs its own circuit. Can your panel take it?

At its full 15A wall draw the Electra Induction Stove needs a 20A or dedicated circuit, not a shared 15A one. Adding a circuit raises the panel question: does the service have room and spare capacity for it?

Source

Circuit data read from the manufacturer: Electra Induction Stove specification, accessed 2026-07-11. Sourced from the manufacturer's product page rather than a spec sheet PDF.

The Electra Induction Stove (ships April 2026, $3,999) is a freestanding range that plugs into a standard 120V outlet and states 120V, 15A. Its 5 kWh battery feeds the burners (1800/1800/900/900 W) and 4900 W oven, all far above the ~12A/1440W wall cap. Electra does not print a NEMA plug type, so none is listed here.

The documents behind these figures, and the code sections this page cites, are named in the source receipt.


Frequently Asked Questions

Can the Electra Induction Stove share a circuit?

On a general-purpose / multi-outlet circuit, 15 A exceeds the 12 A cap for a general-purpose / multi-outlet 15 A circuit (15 A x 80% = 12 A), so it is NOT permitted to share a 15 A circuit; it needs a 20 A circuit or a dedicated individual branch circuit. On a 20A circuit: 15 A is within the 16 A cap for a general-purpose / multi-outlet 20 A circuit (20 A x 80% = 16 A), so it may share that circuit. The rule: NEC 210.23(B)(1) (cord-and-plug equipment not fastened in place, 80% of a general-purpose / multi-outlet branch circuit) with the companion receptacle limit of NEC 210.21(B)(2) and Table 210.21(B)(2). Electra's Breaker Saver can dial the wall draw down to 12A, which sits exactly at the 12A cap, so a dialed-down unit fits a shared 15A circuit.

What breaker and wire does the Electra Induction Stove need?

Size it from the 15A wall / charge draw off the rating plate, never the induction burner kW (those peaks come from the battery). On a dedicated individual branch circuit it takes a 15A breaker on #14 copper with a #14 copper equipment ground. If the battery recharge runs 3 hours or more it is a continuous load and the circuit is sized to 125% (NEC 210.20(A)): 15 x 1.25 = 18.75A, a 20A breaker on #12 copper. GFCI: NEC 2023 210.8(D) requires GFCI protection for the branch circuit or outlet supplying a 120V induction range or drop-in cooktop (210.8(D)(8) "Electric ranges", 210.8(D)(10) "Counter-mounted cooking units") rated 150 volts or less to ground and 60 amperes or less, hardwired or plugged in, wherever it is installed; which edition applies is the one your jurisdiction has adopted.

Does the Electra Induction Stove need a dedicated circuit?

At its full 15A wall draw it exceeds the 12A shared-circuit cap for a 15A circuit (cord-and-plug 80%, NEC 210.23(B)(1)), so it needs a 20A circuit (16A cap) or a dedicated individual branch circuit. Electra plugs into a standard 120V outlet (no renovation required) and states 120V, 15A. It imposes no dedicated-circuit requirement and adds explicit shared-circuit support: the Breaker Saver feature dials the wall draw between 2 and 12 amps to avoid tripping the breaker, the strongest adjustable wall-draw bound on this roster.

How much does the Electra Induction Stove add to my service load?

About 1.8 kVA (15A x 120V), just over the 1-3/4 kW Table 220.55 threshold, so Note 3 applies the Column A single-unit 80% demand factor: 1.8 x 0.80 = 1.44 kW. That is far below the 8 kW Column-C demand a conventional 240V range rated 12 kW or less gets, which is why it can fit a service that could not take another 240V range, where a load calculation shows the room.


Check the Circuit

Confirm against your unit's rating plate: enter the wall / charge draw and the circuit rating to get the shared-circuit verdict and the dedicated wire and breaker.


Other 120V Induction Ranges

Related Tools