Cold Climate Heat Pump Capacity
Mitsubishi P-Series Hyper-Heat (ducted): Heating Capacity at 5F and Below
The MAX heating capacity the Mitsubishi P-Series Hyper-Heat (ducted) holds as it gets cold, from the AHRI-certified NEEP record (AHRI 211259279), with the maintained-% and a balance-point readout.
MAX Capacity by Temperature
Printed rated points for the Mitsubishi P-Series Hyper-Heat (ducted) (AHRI 211259279), each labeled RATED or MAX
Swipe the table sideways to see the rest of its columns. →
| Outdoor temperature | Type | Heating capacity |
|---|---|---|
| 47F | RATED | 40,000 BTU/hr |
| 47F | MAX | 40,000 BTU/hr |
| 17F | MAX | 38,000 BTU/hr |
| 5F | MAX | 38,000 BTU/hr |
| -13F (cold floor) | MAX | 30,400 BTU/hr |
The “will it heat my house at 5F” answer is the MAX at 5F (38,000 BTU/hr), shown next to the rated 47F capacity so you see both. Capacity below -13F is not published for this line, so it is not extrapolated here.
Maintained Capacity at 5F
At 5F the Mitsubishi P-Series Hyper-Heat (ducted) holds 38,000 BTU/hr. That is 95% of its rated 47F capacity (38,000 / 40,000), and 95% of its MAX 47F capacity (38,000 / 40,000). Both are true; the denominator is always stated. NEEP floors its stored percentage to a whole number (95% and 95% respectively); the computed ratio is shown above.
Balance Point & Backup Heat
The balance point is where this model's MAX-capacity curve, interpolated between its printed rows, crosses the load line, which runs from zero at 65F to your full design load at the design temperature. Enter your own design heat load in the calculator below for your numbers. This is a readout, not a substitute for a Manual-J load calculation.
Run It for Your Temperature and Load
Source
Capacity and COP read from the AHRI-certified NEEP cold-climate air-source heat pump database, pinned to AHRI certificate 211259279 for outdoor unit PUZ-HA36NKA: NEEP ccASHP record, accessed 2026-07-29. The manufacturer engineering data or a Manual-J by an HVAC pro has the final say.
The benchmark cold-climate ducted unit: it holds 38,000 BTU/hr at 5F, 95% of its 40,000 rated capacity at 47F, and still puts out 30,400 down to -13F. Mitsubishi markets the line as 100% capacity at 5F, but the AHRI-certified NEEP record prints 95%, which is the honest published number.
The documents behind these figures are listed in the source receipt.
Frequently Asked Questions
What is the Mitsubishi P-Series Hyper-Heat (ducted) heating capacity at 5F?
The Mitsubishi P-Series Hyper-Heat (ducted) puts out 38,000 BTU/hr MAX at 5F, which is 95% of its 40,000 BTU/hr rated capacity at 47F (and 95% of its 40,000 MAX at 47F). This is the number that answers whether it can heat your house on a cold day. Pinned to AHRI certificate 211259279.
How low can the Mitsubishi P-Series Hyper-Heat (ducted) operate?
The lowest rated row on the AHRI-certified NEEP record is -13F, where it still delivers 30,400 BTU/hr MAX. The record rates nothing colder, so for a colder temperature the calculator shows the -13F row's capacity, labelled -13F, and computes no capacity or backup heat at the colder one; read the manufacturer's low-ambient capacity data for it.
What is the Mitsubishi P-Series Hyper-Heat (ducted) COP at 5F?
The COP at MAX capacity at 5F is 2. That is the coefficient of performance at the maximum output the unit reaches at 5F. Only the MAX-capacity COP is published here; the minimum-output COP at extreme lows is artifactual and is not a useful cold-weather figure.
What is the balance point for the Mitsubishi P-Series Hyper-Heat (ducted)?
It depends on your home's heat loss. Against a 45,000 BTU/hr design load at 5F, the Mitsubishi P-Series Hyper-Heat (ducted) balances at 14.3F and needs 7,000 BTU/hr (2.05 kW) of backup heat at the 5F design temperature. Enter your own load in the calculator for your balance point. A Manual-J load calculation has the final say.
Other Cold-Climate Heat Pumps
Bosch IDS (ducted)
21,800 BTU/hr at 5F (63.7% of rated).
Fujitsu AIRSTAGE XLTH (wall ductless)
23,200 BTU/hr at 5F (96.7% of rated).
Carrier Performance (ducted)
26,200 BTU/hr at 5F (82.4% of rated).
Daikin Aurora (wall ductless)
21,600 BTU/hr at 5F (100% of rated).
LG Ceiling / ducted (R-32)
36,000 BTU/hr at 5F (90% of rated).
Gree FLEXX (ducted, R-32)
25,000 BTU/hr at 5F (100% of rated).
MRCOOL Universal (ducted DIY)
22,000 BTU/hr at 5F (91.7% of rated).
Capacity at 5F Chart (All Models)
Every line on one table: rated 47F, MAX at 17F and 5F, the cold floor, and COP.
Related Tools
What Size Mini Split Do I Need
Ductless sizing by room and climate, with the cold-climate heat-pump note.
How Many BTU to Heat a House
Bryant's furnace size per square foot by climate region, a starting estimate; a Manual J calculation gives the design heat load to compare against this model's capacity.
BTU / HVAC Load Calculator
A house's heating load by ACCA Manual J at your ZIP code's weather station, for the balance-point readout.
Superheat & Subcooling Calculator
Verify the charge on the installed system.
A2L Line Set Calculator
Reuse, flush, or replace the line set for an R-454B or R-32 changeout.
MCA / MOCP Calculator
Size the circuit for the unit from its nameplate.