Bending Reference
Rolling Offset Calculator
Find the true offset, mark spacing, roll angle, and shrink for a rolling offset in EMT. The right-triangle formula, a rise-and-roll chart, and the interactive calculator with an SVG diagram.
The Rolling Offset Formula
A rolling offset is a normal offset pointed in a diagonal direction. You solve it in three steps: find the true offset, apply the offset multiplier, then rotate the pipe by the roll angle so it travels the right way.
Mark spacing = true offset × the bender-chart multiplier (2.0 at 30°, 1.4 at 45°; the rounded 1/sin)
Roll angle = arctan(roll / rise)
The bend angle (how sharp each of the two bends is, 30° for example) is different from the roll angle (how far you spin the conduit between bends). Shrink follows the true offset, the same as a straight offset.
Rolling Offset Chart
True offset, mark spacing at the two common bend angles, and the roll angle for common rise-and-roll combinations. Mark spacing = true offset × the bender-chart multiplier (2.0 at 30°, 1.4 at 45°), which is 1/sin rounded to a tape-measure value.
Rolling offset true offset, mark spacing at 30 and 45 degrees, and roll angle, by rise and roll
Swipe the table sideways to see the rest of its columns. →
| Rise | Roll | True Offset | Marks @ 30° | Marks @ 45° | Roll Angle |
|---|---|---|---|---|---|
| 3" | 4" | 5" | 10" | 7" | 53° |
| 4" | 4" | 5.66" | 11.31" | 7.92" | 45° |
| 5" | 5" | 7.07" | 14.14" | 9.9" | 45° |
| 6" | 4" | 7.21" | 14.42" | 10.1" | 34° |
| 6" | 6" | 8.49" | 16.97" | 11.88" | 45° |
| 8" | 6" | 10" | 20" | 14" | 37° |
Calculate Your Rolling Offset
Enter your rise, roll, and bend angle for exact marks, true offset, and shrink with an SVG diagram. The calculator also handles straight offsets, saddles, 90s, and kicks.
Bend type: 15 families, pick one
Common bends
Klein and Gardner Bender EMT hand bender take-up, with NEC Chapter 9, Table 2 radii by trade size. Greenlee's SITE-RITE hand-bender manual rates the same benders for 1/2" through 1-1/4" EMT and 1/2" through 1" rigid and IMC, and its older IM 1071 manual says 1/2" through 1" rigid: pick the type above (1-1/4" is not carried in IMC or RMC: no held bender document bends it by hand).
Shrink per inch of offset:
Show the math
- MATHTrue Offset = √(Rise² + Roll²) = √(4² + 6²) = 7.21"
- MATHTravel = True Offset × chart multiplier (2) = 14.42"
- MATHShrink = 1.8"
Bender charts print a 2.0 multiplier at 30°, which this calculator uses, and exact 1/sin(30°) is the same 2.00, so two bends at that spacing rise exactly the depth you asked for.
Where this number comes fromIntry Verified
- Calculated from
- Bender-chart offset multiplier (2.0), Greenlee and Gardner Bender. Marks and shrink from the bender-chart constants where a manufacturer prints the angle (offset multiplier, 3-point saddle multiplier and shrink per inch) and from bend geometry elsewhere (offset 1/sin, saddle depth/sin(half-angle), kick travel); take-up from the EMT bender profile for your conduit size, or the deduct you entered (the only take-up carried for IMC and RMC), and gain from that conduit's own radius and outside diameter. See the full receipt ↓
- Run with
- BendRolling Offset
- Setuprise 4" / roll 6" @ 30°
- Checked
- Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 35,938 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site holds, read from the bender chart or geometry it was computed from and the NEC Chapter 9 Table 2 radius. This is our own deterministic gate, not a third-party audit.
- Final say
- Field-verify against the actual bend. Bender take-up varies by tool and shoe.
Intry Verified · Build 525536D · 2026-11-13
Next on this job
This run travels with its receipt: 1/2" EMT, Rolling Offset, 2 marks, developed length 14.42".
- Conduit fillCarries 1/2" EMT into the fill calculator; add the conductors you are pulling.
- Wire sizeCarries the receipt only: a bend run knows no load, so enter the amps, voltage and one-way distance there.
- Box fillCarries the receipt only: a bend run knows no box, so enter the box and its conductors there.
One question
Did this help you on the job?
Worked Example: 4-Inch Rise, 4-Inch Roll at 30 Degrees
Given: Conduit must move up 4 inches and over 4 inches to meet a box, using 1/2" EMT and 30-degree bends.
Step 1: True offset. √(4² + 4²) = √32 = 5.66 inches.
Step 2: Mark spacing. 5.657 / sin(30°) = 5.657 × 2.0 = 11.31 inches between the two marks.
Step 3: Roll angle. arctan(4 / 4) = 45°. Rotate the conduit 45 degrees between the first and second bend so the offset travels on the diagonal.
Result: Two 30-degree bends 11.31" apart, rolled 45°, with about 1.4" of shrink (5.66 × 1/4").
Frequently Asked Questions
How do you calculate a rolling offset?
A rolling offset combines a vertical rise and a horizontal roll into one offset. First find the true offset (the straight-line distance the conduit actually travels) with the right-triangle formula: true offset = square root of (rise squared + roll squared). Then treat it like a normal offset: mark spacing = true offset x the bender-chart multiplier for the angle (2.0 at 30 degrees, 1.4 at 45), which is 1/sin rounded to a tape-measure value; the exact 1/sin is 2.00 and 1.41. For a 3-inch rise and 4-inch roll, true offset = square root of (9 + 16) = 5 inches, and at 30 degrees the marks are 5 x 2.0 = 10 inches apart.
What is the true offset in a rolling offset?
The true offset is the actual straight-line distance between the start and end of the offset, accounting for both the rise (vertical) and the roll (horizontal). It is the hypotenuse of a right triangle whose legs are the rise and the roll: true offset = square root of (rise squared + roll squared). You always bend to the true offset, not to the rise or roll alone, or the conduit will not land where you need it.
What is the roll angle in a rolling offset?
The roll angle is how far you rotate the conduit around its own axis between the two bends so the offset travels in the correct diagonal direction. It equals the arctangent of roll divided by rise. For a 3-inch rise and 4-inch roll, the roll angle is arctan(4/3) = about 53 degrees from vertical. The bend angle (how sharp each bend is, such as 30 degrees) is separate from the roll angle (which direction the offset points).
When do you use a rolling offset?
You use a rolling offset when the conduit has to change position in two directions at once, for example moving up and over to meet a box that is both higher and off to the side. Instead of making a separate vertical offset and horizontal offset, one rolling offset handles both in two bends. It applies on conduit racks, in mechanical rooms, and anywhere pipe transitions between planes that are not square to each other.
Does the rolling offset shrink the conduit?
Yes, the same as a normal offset. Shrink is based on the true offset and the bend angle: multiply the true offset by the shrink-per-inch constant for the angle (1/4 inch per inch at 30 degrees). For a 5-inch true offset at 30 degrees, shrink = 5 x 1/4 = 1.25 inches. Subtract that when measuring from a reference point so the finished run lands in the right spot.
More Bending References
Conduit Bending Calculator
Every bend family the calculator carries as an interactive 3D rendering or flat diagram, with verified bender profiles.
Offset Multiplier Chart
Multipliers and shrink per inch for 10° through 60° offset bends.
Conduit Shrink Calculator
Shrink per inch of offset and kick by angle, and why pipe size does not change it.
Saddle Bend Calculator
3-point and 4-point saddle marks, spacing multipliers, and shrink.