NEC 705.12(B)(2) · 240.6(A)
Can My Panel Handle Solar?
The biggest solar backfeed breaker your busbar can take under the NEC 705.12 120% rule, worked by busbar and main size, and which panels need a line-side connection instead.
Max solar backfeed breaker, by busbar and main
Find your panel's busbar rating down the left and your main breaker across the top. The cell is the largest standard backfeed breaker the 120% rule allows, with the continuous inverter output it supports (breaker ÷ 1.25) below it.
| Busbar | 100A main | 125A main | 150A main | 200A main |
|---|---|---|---|---|
| 100A bus | 20 A16 A inverter | n/a | n/a | n/a |
| 125A bus | 50 A40 A inverter | 25 A20 A inverter | n/a | n/a |
| 150A bus | 80 A64 A inverter | 50 A40 A inverter | 30 A24 A inverter | n/a |
| 200A bus | 125 A100 A inverter | 110 A88 A inverter | 90 A72 A inverter | 40 A32 A inverter |
| 225A bus | 150 A120 A inverter | 125 A100 A inverter | 110 A88 A inverter | 70 A56 A inverter |
Each breaker is 120% of the busbar less the main, rounded DOWN to a standard 240.6(A) size (a raw 140A allowance becomes a 125A breaker, a raw 55A becomes 50A). The inverter figure is the breaker ÷ 1.25, the continuous output the breaker supports. The branch conductors to the inverter are sized separately, at 125% of the inverter output.
Scope: read this before you size anything
This is the opposite-end 120% configuration: a utility main at one end of the busbar and the solar breaker at the far end, with the required “do not relocate” label. Confirm the busbar rating on the panel label (it can differ from the main or the panel's marketing rating) and the opposite-end placement before you size anything.
The matrix assumes the only two sources on the bus are the utility main and this one solar breaker. If the panel already carries any other backfed source – a battery inverter, a second PV array, a generator interlock – you must subtract 125% of each of those too, because the 120% allowance covers the main plus every backfeed breaker, not the main alone. And the 120% rule applies to every busbar in the backfeed path: if this panel feeds through to a subpanel, that subpanel busbar and the feed-through conductors must pass it too – a downstream busbar can be the real limit.
It does not cover main-lug-only panels (no main to bound the bus, they use the 100% sum rule of 705.12(B) instead), center-fed, or split-bus panels. When no standard breaker fits, the path is a supply-side (line-side) connection per NEC 705.11 ahead of the main, or a listed power control system (NEC 705.13) that caps bus current – either can add a larger system without a service upgrade.
The check, worked (NEC 705.12 120% rule)
Take 120% of the busbar ampacity, subtract the main breaker rating, and round the result down to a standard breaker. A 200A busbar: 120% × 200 = 240A allowed on the bus. Subtract a 200A main and 40A is left, which is already a standard 40A breaker. That breaker supports an inverter up to 40 ÷ 1.25 = 32A continuous, about 7.7 kW at 240V. If instead the main were a derated 150A, the room grows to a 90A breaker. Every number on this page is computed by the same locked engine the load calculator runs, recomputed from the locked NEC 705.12 and Table 240.6(A) rules on every deploy.
Check your own panel
Enter the busbar rating off the panel label and the rating stamped on the main breaker. The engine is the same one every cell of the matrix above was computed with.
Intry VerifiedA worked default reading, traceable end to end: what it was calculated from, what it was run with, how it was checked, and who has final say.
Where this number comes fromIntry Verified
- Calculated from
- NEC 705.12(B)(2) 120% rule, standard ratings from 240.6(A). Computed from the NEC 705.12(B)(2) 120% busbar allowance, rounded down to a standard 240.6(A) breaker and held to the busbar rating; where the backfeed is NOT at the opposite end of the bus, 705.12(B)(1) governs instead at 100% and gives a smaller breaker than this. See the full receipt ↓
- Run with
- Busbar rating200 A
- Main OCPD200 A
- Supply arrangementOpposite ends of the busbar
- Checked
- Every figure an Intry calculator computes comes from a locked source module, not hand-typed. 30639 automated checks, one suite for the whole site rather than a per-tool count, re-derive the numbers before each deploy from the tables this site transcribed from the cited NEC section. This is our own deterministic gate, not a third-party audit.
- Final say
- Your AHJ and the utility interconnection agreement have final say; confirm the panel's busbar rating and that the backfeed sits at the opposite end of the bus from the main.
Intry Verified · NEC 2023 · Build 8232217 · 2026-10-06
New: run this inside your AI assistant
Prefer to just ask? Add this to Claude, free.
Connect Intry to Claude once, then just say “use Intry to…” to run the solar backfeed breaker calculator from a plain-English question, on your phone, on the job. You get the number (computed live, not guessed), what it means, and the cited NEC section. Works on every Claude plan.
Frequently Asked Questions
Can my 200A panel handle solar?
Almost always. By the NEC 705.12(B)(2) 120% rule, a 200A busbar allows 120% x 200 = 240A of total supply. Subtract a 200A main and 40A of room is left for a backfed solar breaker, which rounds down to a standard 40A breaker (NEC 240.6(A)). That supports a 32A continuous inverter output, roughly 7.7 kW at 240V, which covers a typical residential system. If your main is smaller than the busbar (a derated or subpanel main), the room grows: a 200A bus with a 150A main leaves room for a 90A breaker. This assumes nothing else is already backfeeding the bus: if the panel already has a PV or battery breaker, subtract 125% of that too, since the 120% allowance covers the main plus every backfed source.
What is the 120% rule for solar?
It is NEC 705.12(B)(2). Where the utility main and a backfed solar breaker sit at OPPOSITE ends of a busbar that carries loads, the sum of 125% of the source output current and the busbar's overcurrent device (the main) must not exceed 120% of the busbar ampacity. In practice, because the backfed breaker is already sized at 125% of the inverter's continuous output, installers apply it as: max solar breaker = (120% x busbar) minus the main, rounded down to a standard breaker size. The extra 20% headroom is the buffer that keeps the bus from overheating when both sources push current at once.
Why do I round the backfeed breaker down and not up?
Because the 120% figure is a ceiling on the total, not a breaker size. A 200A bus with a 200A main leaves 40A of room, and 40A happens to be a standard breaker. But a 200A bus with a 100A main leaves 140A of room, and 140A is not a standard breaker, so it rounds DOWN to 125A per NEC 240.6(A). Rounding up would exceed the 120% ceiling and overload the bus. Rounding down is the conservative, universally taught practice: the breaker is always at or below the room the code allows.
What if no breaker fits, or my panel is main-lug-only?
Then the load-side (120%) method is not your path, and that is a real answer, not a failure. If the main already uses the full 120% allowance, or the panel is main-lug-only (no main breaker to bound the busbar), you have two routes: a supply-side (line-side) connection per NEC 705.11, tapping ahead of the main, or a listed power control system (NEC 705.13) that actively limits bus current and can fit a larger PV-plus-battery system without a service upgrade. A main-lug-only panel actually uses the 100% sum rule (705.12(B)), not the 120% rule. Center-fed and split-bus panels are also excluded from the simple 120% form. This tool covers the standard opposite-end 120% configuration.
Does the backfeed breaker size equal my inverter size?
No, and mixing them up is the common mistake. The matrix gives the max BACKFEED BREAKER. The inverter's continuous output current is the breaker divided by 1.25 (the breaker is 125% of the continuous output). So a 40A backfeed breaker supports up to a 32A continuous inverter, about 7.7 kW at 240V. Size the breaker from this rule; size the inverter (or the number of microinverters) to stay at or under the breaker's supported current.
Related Calculators
Can My Panel Handle It?
The same headroom check for an EV charger, heat pump, water heater, or induction range.
Dwelling Load Calculator
The NEC 220.82 / 220.87 service calc: what your existing loads already draw before you add generation or a new load.
Standard Breaker Sizes
The NEC 240.6(A) standard OCPD ratings the backfeed breaker rounds down to.
Biggest EV Charger
The other side of panel headroom: the largest EV charger a service can take by NEC 220.87.