120V Induction Range Circuit
Portable vs Battery-Buffered vs 240V: Which “120V Induction Range”?
“A 120V induction range” means three different things, and they need three different circuits. Here is the canonical distinction, and how to wire each one.
The Three, Side by Side
The three appliances people call a “120V induction range” and the circuit each needs
Swipe the table sideways to see the rest of its columns. →
| Portable countertop | Battery-buffered 120V range | Conventional 240V range | |
|---|---|---|---|
| What it is | A 1-2 burner countertop appliance, no battery | A full-size freestanding range/cooktop with an integrated battery | A standard 240V freestanding range |
| Examples | Countertop single/double induction burners | Copper Charlie Induction Range, Impulse Cooktop, Electra Induction Stove | Any conventional electric/induction range |
| Wall draw | Up to 15A (~1.4-1.8 kVA) | 12-15A at 120V | 40A at 240V |
| Burner power | Limited to the wall feed | 5-10 kW peaks from the battery | Full power from the circuit |
| Circuit | Any 120V outlet | 15A / 120V branch (#14 Cu) | 40A / 240V range circuit (#8 Cu) |
| Share a circuit? | Yes, within 12A/15A (16A/20A) | Freestanding range: within the 80% cap (a 15A unit needs 20A or dedicated). Drop-in cooktop (fixed): 50% cap; more than half of a 20A circuit, dedicated | Only with other cooking appliances fastened in place (210.23(D)) |
| Replaces a 240V range? | No | Yes | n/a |
| Service load | ~1.44 kVA | ~1.44-1.44 kW | 8 kW (Column C, a range of 12 kW or less) |
The battery-buffered and 240V figures are manufacturer-stated wall draws and NEC-derived circuits. The portable figure is the 15A receptacle ceiling any cord-and-plug appliance is bound by (NEC 210.23(B)(1) / Table 210.21(B)(2)).
Why the Battery Is the Whole Difference
A portable countertop cooktop and a battery-buffered range can draw the same 12 to 15A from the same 120V outlet, but only one cooks like a range. The integrated battery in the full-size class stores energy between and during cooking and releases it in bursts, so a burner can deliver 5 to 10 kW even though the wall never supplies more than about 1.8 kW. A portable unit has no reservoir, so its burner power is capped at whatever the 15A feed can push at that instant. That is why a 15A battery range replaces a 240V range and a 15A portable cooktop does not.
The Circuit Each Needs
All three are governed by the same shared-circuit rule on the 120V side: a cord-and-plug appliance not fastened in place is capped at 80% of a general-purpose / multi-outlet branch circuit (NEC 210.23(B)(1)), so 12A on a 15A circuit and 16A on a 20A. A 12A battery range or a modest portable (shares at the appliance limit) rides an existing 15A circuit at the cap; a 15A battery range or a full 15A portable (needs a 20a or dedicated circuit). The conventional 240V range steps outside this rule: a range of 8-3/4 kW or more takes a 40A / 240V minimum (NEC 210.19(C)), and a 40- or 50-ampere circuit with more than one outlet may supply only cooking appliances fastened in place in a dwelling (210.23(D)).
The code sections this page cites are named in the source receipt.
Frequently Asked Questions
What is the difference between a portable induction cooktop and a 120V induction range?
A portable induction cooktop is a countertop appliance with one or two burners that plugs into any 120V outlet and draws up to the 15A the receptacle allows (about 1.4 to 1.8 kVA). It cannot cook like a full range. A battery-buffered 120V induction RANGE (Copper Charlie, Impulse Cooktop, Electra) is a full-size freestanding range or cooktop with an integrated battery: the burners deliver 5 to 10 kW of peak power from the battery while the wall side draws only 12 to 15A. Same 120V plug, completely different appliance.
Can a battery-buffered 120V range really replace a 240V range?
Yes, that is the point of the class. The integrated battery decouples the burners from the wall, so the range delivers full 240V-class burner power (5 to 10 kW peaks) while drawing only 12 to 15A from an ordinary 120V branch circuit. A portable countertop unit cannot, because it has no battery and is limited to what the 15A wall feed supplies at any instant.
How do I wire each one?
A portable countertop cooktop needs no special wiring; it plugs into an existing 120V outlet, and on a shared circuit it is capped at 12A (15A circuit) or 16A (20A) like any cord-and-plug not-fastened appliance (NEC 210.23(B)(1) 80%). A battery-buffered 120V freestanding range runs on a 15A / 120V branch circuit (a 12A unit on #14 Cu) with the same 80% cap, so a 15A range wants a 20A or dedicated circuit; a drop-in cooktop is fixed in place, so the stricter NEC 210.23(B)(2) 50% cap governs, and one drawing more than half of a 20A circuit needs a dedicated circuit. A conventional 240V range takes a 40A / 240V circuit on #8 Cu, the NEC 210.19(C) minimum for a range of 8-3/4 kW or more. GFCI: NEC 2023 210.8(D) requires GFCI protection for the branch circuit or outlet supplying a 120V induction range or drop-in cooktop (210.8(D)(8) "Electric ranges", 210.8(D)(10) "Counter-mounted cooking units") rated 150 volts or less to ground and 60 amperes or less, hardwired or plugged in, wherever it is installed; which edition applies is the one your jurisdiction has adopted.
Which one adds the least to my service load?
A portable countertop unit and a battery-buffered 120V range both add only about 1.44 to 1.8 kVA to the service calculation (under or just over the 1-3/4 kW Table 220.55 threshold). A conventional 240V range adds 8 kW (Table 220.55 Column C). So either 120V option can fit a service that could not take another 240V range, where a load calculation shows the room.
Go Deeper
120V Induction Range Circuit Hub
Every unit with its wall draw, shared verdict, and dedicated circuit, plus the calculator.
120V vs 240V
The plug-in class next to a conventional 240V range: circuit, wiring, and recovery.
Breaker & Wire Chart
Every unit on one table: wall draw, shared verdict, dedicated breaker and wire.
Appliance Amps
Running amps for household appliances, each sourced row naming the model it is read from, and the circuit each needs.
Keep going