NEC Article 430 (Motors) + Article 680 (Pools)
What Size Wire for a Pool Pump?
A pool pump is a motor load, and it carries the extra pool rules: GFCI protection, an 8 AWG equipotential bond, and a disconnect within sight. Here is the wire and breaker by horsepower, the pool requirements, and the calculator.
Motor Sizing, Then the Pool Rules on Top
First the motor: the conductor carries 125% of the pump's table full-load current (NEC 430.22) and an inverse-time breaker may be up to 250% of it (430.52), sized from the FLC in Table 430.248, not the advertised horsepower. Then Article 680 adds three things a pool pump needs that an ordinary motor does not: GFCI protection for the pump circuit (680.21(C)), a separate 8 AWG solid copper equipotential bonding conductor tying the motor to the pool bonding grid (680.26, this is not the circuit ground), and a disconnecting means within sight of the pump and at least 5 feet from the inside walls of the pool (680.13).
Pool Pump Wire and Breaker by Horsepower (240V)
Single-phase 240V single-speed pump, copper. FLC from NEC Table 430.248. GFCI required.
Swipe the table sideways to see the rest of its columns. →
| Pump HP | FLC (430.248) | Min Wire (430.22) | Max Breaker (430.52) | Ground (680.7(A)) |
|---|---|---|---|---|
| 1/2 HP | 4.9 A | #14 | 15 A | #12 |
| 3/4 HP | 6.9 A | #14 | 20 A | #12 |
| 1 HP | 8 A | #14 | 20 A | #12 |
| 1-1/2 HP | 10 A | #14 | 25 A | #10 |
| 2 HP | 12 A | #14 | 30 A | #10 |
“Min Wire” is the code minimum by ampacity (60°C column). The breaker shown is the maximum inverse-time size and must be a GFCI type; a maker's smaller listed breaker governs (the table below). The 8 AWG equipotential bond (680.26) is separate from the ground column above. A variable-speed pump is sized from its drive nameplate: Hayward's Super Pump VS lists 0.4 to 10.0 A on a 15 amp branch circuit.
On several rows the ground is larger than the circuit conductor, and on a motor circuit that is expected: NEC 430.52 sizes the breaker for locked-rotor inrush at up to 250 percent of full-load current while 430.22 sizes the conductor at 125 percent, and Table 250.122 sizes the ground from the breaker. On a pool pump circuit NEC 680.7(A) also sets a floor: an insulated copper ground “not smaller than 12 AWG”. The Ground column prints the larger of Table 250.122's size and that floor. NEC 250.122(A) says the grounding conductor is “not required to be larger than the circuit conductors supplying the equipment”, and some inspectors read that as permitting a smaller ground on these rows; on this circuit that reading never goes below the 12 AWG floor, and we do not publish it as the answer. Ask your AHJ before downsizing, and keep the ground at 12 AWG copper or larger.
The ground on a pool pump circuit has its own floor: NEC 680.7(A) requires branch circuits in a corrosive environment or wet location to contain an equipment grounding conductor that is an insulated copper conductor sized by Table 250.122, “but not smaller than 12 AWG”. The Ground column applies it (the 1/2 HP row's 15 A breaker takes #14 under Table 250.122 alone), and the 250.122(A) relief above stops at that floor.
One Maker's Table: Hayward Super Pump at 230V
Hayward's “Electrical Guide, 60 Cycle Motors, Single Phase” (Super Pump owner's manual, 230V rows), beside the NEC 430.52 maximum for each HP.
Swipe the table sideways to see the rest of its columns. →
| Motor HP | Hayward Breaker | Hayward Wire (0-50 ft) | NEC Max Breaker (430.52) |
|---|---|---|---|
| 3/4 HP | 10 A | No. 14 | 20 A |
| 1 HP | 10 A | No. 14 | 20 A |
| 1-1/2 HP | 15 A | No. 14 | 25 A |
| 2 HP | 15 A | No. 14 | 30 A |
| 2-1/2 HP | 20 A | No. 12 | not computed here |
Size Your Exact Pump
It opens on the 15 A circuit Hayward lists for its 1-1/2 and 2 HP Super Pump at 230 V above. For your pump, enter the Table 430.248 full-load current for its horsepower, or the nameplate full-load current if the pump is marked with both horsepower and full-load current, and turn Continuous load on: it applies the 125% NEC 430.22 requires. The breaker line is a general-circuit value, not the NEC 430.52 motor breaker. Its ground line applies NEC 680.7(A): an insulated copper conductor sized by Table 250.122 and not smaller than 12 AWG, and a link you save or share keeps that rule. For the run to the equipment pad, the result links to the voltage drop calculator, which checks that wire over your run; this tool does not size for voltage drop.
The code sections this page cites are named in the source receipt.
Frequently Asked Questions
What size wire do I need for a pool pump?
A pool pump is a motor load under NEC Article 430 with extra pool rules from Article 680. Hayward's Super Pump manual lists its 1 to 2 HP motors at 230V on 10 to 15A circuit breakers with No. 14 copper for runs up to 50 ft; Hayward's table goes to No. 12 on a 20A breaker at 2-1/2 HP. The code-minimum conductor by ampacity is 125% of the table full-load current (430.22), the Min Wire column below; over a longer run to the equipment pad, check voltage drop. For variable-speed pumps, Hayward's Super Pump VS lists 0.4 to 10.0 A at 230V and says to connect it to a 15 amp branch circuit, and Pentair's SuperFlo VS regulates its speed when running on lower voltage to keep current below 13.2 A. Always confirm the pump's nameplate amps, and remember the whole circuit must be GFCI-protected (680.21(C)).
Does a pool pump need a GFCI?
Yes. NEC 680.21(C) requires ground-fault protection for outlets serving pool motors: GFCI protection or SPGFCI protection, as applicable (a listed low-voltage motor is the exception). For a hardwired 240V pump that is a GFCI breaker at the panel (Pentair's SuperFlo VS manual says to connect the pump only to a supply circuit protected by a GFCI circuit breaker); a cord-and-plug pump can take a GFCI receptacle. This is on top of the motor branch-circuit sizing, not a substitute for it.
What is the pool pump bonding wire, and is it the same as the ground?
No, it is a separate conductor. NEC 680.26 requires an 8 AWG solid copper equipotential bonding conductor that ties the pump motor, metal pool parts, ladders, rails, and the surrounding deck reinforcement into one bonded grid, so everything sits at the same potential and no dangerous voltage can appear across a swimmer. That 8 AWG solid bond is in addition to the equipment grounding conductor that runs with the circuit; the two do different jobs. Hayward's Super Pump manual tells the electrician to “Run a continuous wire from external bonding lug to reinforcing rod or mesh”, and Pentair's SuperFlo VS manual to bond “Using the Bonding Lug located on the side of the motor”.
What size breaker for a pool pump?
Size it from the motor's full-load current, not the nameplate horsepower marketing. An inverse-time breaker may be up to 250% of the table FLC (NEC 430.52), which at 230V is 20A for 1 HP, 25A for 1-1/2 HP and 30A for 2 HP. That is a ceiling, not a target: Hayward's Super Pump manual lists 10 to 15A breakers for those motors, and the maker's instructions govern (NEC 110.3(B)). It must be a GFCI breaker (or the circuit otherwise GFCI-protected) per 680.21(C). A disconnecting means must also be within sight of the pump and at least 5 feet from the inside pool walls (NEC 680.13).
Are variable-speed pool pumps wired differently?
The rules are the same, and the numbers come from the drive's nameplate. Federal DOE standards (10 CFR 431.465(f)) hold each “dedicated-purpose pool pump that is not a submersible pump and is manufactured starting on July 19, 2021” to a minimum weighted energy factor (WEF), with self-priming pool filter pumps from 0.711 hp to under 2.5 hp of rated hydraulic horsepower in their own class. Two named ones: Hayward's Super Pump VS lists 0.4 to 10.0 A at 230V on a 15 amp branch circuit, and Pentair's SuperFlo VS regulates its speed when running on lower voltage to keep current below 13.2 A, with terminals taking up to 10 AWG wire, and Pentair offers a 2-pole 20 amp GFCI breaker for it. The GFCI, the 8 AWG equipotential bond, and the within-sight disconnect still apply exactly the same. Size the conductor from the drive's nameplate input amps.
Related
Can My Panel Handle It?
Before you add this load, the NEC 220.87 check on whether the service can carry it.
Well Pump Wire Size
Another motor load, with the voltage-drop upsizing over the well depth.
Hot Tub Wire Size
50A GFCI circuit under NEC Article 680, with the same disconnect rule.
Wire Size for Appliances
Dryer, range, water heater, AC, and more: the circuit for each.
Wire Size Calculator
Size any load per NEC 310.16 with derating, then check voltage drop.