NEC Article 430 (Motors) + Article 680 (Pools)
What Size Wire for a Pool Pump?
A pool pump is a motor load, and it carries the extra pool rules: GFCI protection, an 8 AWG equipotential bond, and a disconnect within sight. Here is the wire and breaker by horsepower, the pool requirements, and the calculator.
Motor Sizing, Then the Pool Rules on Top
First the motor: the conductor carries 125% of the pump's table full-load current (NEC 430.22) and an inverse-time breaker may be up to 250% of it (430.52), sized from the FLC in Table 430.248, not the advertised horsepower. Then Article 680 adds three things a pool pump needs that an ordinary motor does not: GFCI protection for the pump circuit (680.21(C)), a separate 8 AWG solid copper equipotential bonding conductor tying the motor to the pool bonding grid (680.26, this is not the circuit ground), and a disconnecting means within sight of the pump and at least 5 feet from the inside walls of the pool (680.12).
Pool Pump Wire and Breaker by Horsepower (240V)
| Pump HP | FLC (430.248) | Min Wire (430.22) | Max Breaker (430.52) | Ground |
|---|---|---|---|---|
| 1/2 HP | 4.9 A | #14 | 15 A | #14 |
| 3/4 HP | 6.9 A | #14 | 20 A | #14 |
| 1 HP | 8 A | #14 | 20 A | #14 |
| 1-1/2 HP | 10 A | #14 | 25 A | #14 |
| 2 HP | 12 A | #14 | 30 A | #14 |
“Min Wire” is the code minimum by ampacity (60°C column); #12 copper is the common real-world pick on a 20A circuit. The breaker shown is the maximum inverse-time size and must be a GFCI type. The 8 AWG equipotential bond (680.26) is separate from the ground column above. Variable-speed pumps draw less; size from the drive nameplate.
Size Your Exact Pump
Enter the pump nameplate amps as the load (use 125% for the conductor) and your run to the equipment pad to check voltage drop.
Frequently Asked Questions
What size wire do I need for a pool pump?
A pool pump is a motor load under NEC Article 430 with extra pool rules from Article 680. A typical single-speed 1-2 HP pump is 240V and lands on a 20A breaker; the code-minimum conductor by ampacity is #14 copper (125% of the table full-load current, 430.22), but #12 copper is the common real-world choice for margin and voltage drop over the run to the equipment pad. Variable-speed pumps draw less and are often on a 15-20A circuit as well. Always confirm the pump's nameplate amps, and remember the whole circuit must be GFCI-protected (680.21(C)).
Does a pool pump need a GFCI?
Yes. NEC 680.21(C) requires GFCI protection for the outlet supplying any pool pump motor on a branch circuit rated 150 volts or less to ground and 60 amperes or less, single- or three-phase. That is satisfied by a GFCI breaker at the panel (common for a hardwired 240V pump) or a GFCI receptacle for a cord-and-plug pump. This is on top of the motor branch-circuit sizing, not a substitute for it.
What is the pool pump bonding wire, and is it the same as the ground?
No, it is a separate conductor. NEC 680.26 requires an 8 AWG solid copper equipotential bonding conductor that ties the pump motor, metal pool parts, ladders, rails, and the surrounding deck reinforcement into one bonded grid, so everything sits at the same potential and no dangerous voltage can appear across a swimmer. That 8 AWG solid bond is in addition to the equipment grounding conductor that runs with the circuit; the two do different jobs. Many pool motors have a dedicated external bonding lug for it.
What size breaker for a pool pump?
Size it from the motor's full-load current, not the nameplate horsepower marketing. An inverse-time breaker may be up to 250% of the table FLC (NEC 430.52); a 1-1.5 HP 240V pump runs on a 20-25A breaker and a 2 HP on 30A, and it must be a GFCI breaker (or the circuit otherwise GFCI-protected) per 680.21(C). A disconnecting means must also be within sight of the pump and at least 5 feet from the inside pool walls (NEC 680.12).
Are variable-speed pool pumps wired differently?
The rules are the same, but the numbers are smaller. Variable-speed pumps (now required for most new and replacement residential filtration pumps under federal DOE efficiency rules) draw less current than the old single-speed motors, so many run on a 15A or 20A 240V circuit with #14 or #12 copper. The GFCI, the 8 AWG equipotential bond, and the within-sight disconnect still apply exactly the same. Size the conductor from the drive's nameplate input amps.
Related
Well Pump Wire Size
Another motor load, with the voltage-drop upsizing over the well depth.
Hot Tub Wire Size
50A GFCI circuit under NEC Article 680, with the same disconnect rule.
Wire Size for Appliances
Dryer, range, water heater, AC, and more: the circuit for each.
Wire Size Calculator
Size any load per NEC 310.16 with derating and voltage drop.