NEC Article 430 (Motors)
What Size Wire for a Well Pump?
A well pump is a motor, so it follows NEC Article 430, not the flat appliance rule. Here is the code-minimum wire and breaker by horsepower, why voltage drop can upsize the wire, and the calculator for your run.
Motor Sizing: Two Rules, Two Different Numbers
A motor branch circuit sizes the conductor and the breaker separately, and both start from the table full-load current (FLC) in NEC Table 430.248, not the nameplate amps (NEC 430.6(A)(1)). The conductor only has to carry 125% of the FLC (NEC 430.22). The breaker may be as large as 250% of the FLC (NEC 430.52), because it has to pass the motor's starting inrush without tripping. That is why a well pump can legally have small wire on a much larger breaker: NEC 240.4(G) exempts motor conductors from the small-conductor limits, and a separate overload device (430.32), which can sit inside the pump or its control box, protects the conductor from an overworked motor.
Well Pump Wire and Breaker by Horsepower (240V)
Single-phase 240V submersible/jet pump, copper. FLC from NEC Table 430.248.
Swipe the table sideways to see the rest of its columns. →
| Pump HP | FLC (430.248) | Min Wire (430.22) | Max Breaker (430.52) | Ground |
|---|---|---|---|---|
| 1/2 HP | 4.9 A | #14 | 15 A | #14 |
| 3/4 HP | 6.9 A | #14 | 20 A | #12 |
| 1 HP | 8 A | #14 | 20 A | #12 |
| 1-1/2 HP | 10 A | #14 | 25 A | #10 |
| 2 HP | 12 A | #14 | 30 A | #10 |
“Min Wire” is the code minimum by ampacity at the 60°C column (always-safe / NM-B). The breaker is the maximum inverse-time size; a smaller standard breaker is fine if it reliably starts the pump. Voltage drop on a long run can call for a larger conductor than the minimum, so treat the table as a floor.
On several rows the ground is larger than the circuit conductor, and on a motor circuit that is expected: NEC 430.52 sizes the breaker for locked-rotor inrush at up to 250 percent of full-load current while 430.22 sizes the conductor at 125 percent, and Table 250.122 sizes the ground from the breaker. We publish the table minimum. NEC 250.122(A) also says the grounding conductor is “not required to be larger than the circuit conductors supplying the equipment”, and that is read by some inspectors as permitting the smaller conductor on exactly these rows. It is a defensible reading and we do not publish it as the answer, because a ground larger than the table is never a violation and a ground smaller than it may be. Ask your AHJ before downsizing.
Voltage Drop Can Set the Wire, Not Ampacity
A submersible pump sits at the bottom of the well, so the cable run is the drop depth plus the horizontal run to the panel. Over a long run the code-minimum #14 can lose far more than the 3% target and the motor would run hot and short-lived. That is why pump manufacturers (Franklin, Grundfos, Goulds) publish wire-size charts by horsepower and total run length. The calculator below opens on the 20 A well pump circuit and sizes by ampacity only. Its result links to the voltage drop calculator, which checks that wire over your run; if the drop is too high, size up there, and use the larger of that wire and the NEC 430.22 minimum. Its breaker line is a general-circuit value, not the NEC 430.52 motor breaker.
Enter the motor's Table 430.248 full-load current as the load and turn Continuous load on (the NEC 430.22 125%), then follow the result's voltage drop link with your one-way run, or open the voltage drop calculator →
The code sections this page cites are named in the source receipt.
Frequently Asked Questions
What size wire do I need for a well pump?
A well pump is a motor load, so the wire follows NEC Article 430, not the appliance rule. The branch-circuit conductor only has to carry 125% of the motor's full-load current from NEC Table 430.248 (430.22), which for a 1/2-1 HP 240V submersible is a code-minimum of #14 copper. In practice, though, well pump wire can need upsizing to #12 or #10 copper, because the cable runs down the well and the voltage drop over that depth can starve the motor; a wire-type ground goes up in proportion with them (NEC 250.122(B)). Pump manufacturers publish wire charts by horsepower and total run length; size to that, and never smaller than the NEC 430.22 minimum.
What size breaker for a well pump?
Size the breaker from the motor's table full-load current (FLC), not the nameplate. An inverse-time breaker may be as large as 250% of the FLC (NEC 430.52, Table 430.52(C)(1)), rounded up to the next standard size. A 1/2 HP 240V pump (4.9A FLC) lands on a 15A breaker; 3/4-1 HP on 20A; 1.5 HP on 25A; 2 HP on 30A. The breaker can be larger than the wire's ampacity so the motor can start; the pump's own thermal overload or the control-box overload protects the conductor (430.32), not the branch breaker.
Why is the well pump breaker bigger than the wire can handle?
Because motor circuits split the two jobs. The branch-circuit breaker (NEC 430.52) only provides short-circuit and ground-fault protection, and it has to pass the motor's starting inrush without tripping, so it is sized up to 250% of the FLC. Overload protection, the part that actually protects the small conductor from a stalled or overworked motor, is a separate device sized at 115-125% of the nameplate FLA (430.32), which can be built into the pump or its control box. NEC 240.4(G) specifically exempts motor conductors from the small-conductor breaker limits of 240.4(D), so #14 copper on a 30A motor breaker is code-correct.
Is a well pump 120V or 240V?
Either, by the motor: a submersible can be 240V, and a jet pump can be dual-voltage (wired 120V or 240V). Running a pump at 240V halves the current and the voltage-drop loss over a long cable run. Check the motor or control-box label for the connected voltage before sizing.
Does a well pump need a disconnect?
Yes. NEC 430.102 requires a disconnecting means within sight of the pump motor (or its controller), and the pressure switch is not a disconnect. Submersible pumps are controlled by a pressure switch and, for a 3-wire pump, a control box, but a lockable breaker or a separate disconnect still has to serve as the motor disconnect.
Related
Can My Panel Handle It?
Before you add this load, the NEC 220.87 check on whether the service can carry it.
Voltage Drop Calculator
Size the pump cable for the run down the well and back to the panel.
Pool Pump Wire Size
Another motor load, plus the NEC 680 GFCI and bonding rules.
Wire Size for Appliances
Dryer, range, water heater, AC, and more: the circuit for each.
Wire Size Calculator
Size any load per NEC 310.16 with derating, then check voltage drop.