NEC Article 440 (Air Conditioning)

What Size Wire for a Central Air Conditioner?

A central AC or heat pump is sized to the nameplate, not the tonnage. Here is how to read the MCA and MOCP, the typical ranges by size, and the calculator to size your exact unit.

Quick answer: Size the wire to the nameplate MCA (minimum circuit ampacity) and the breaker to the MOCP (max overcurrent protection), never to the tonnage. A typical 2-3 ton unit is #10 copper on a 30-35A breaker; a 4-5 ton can need #8. Two same-tonnage units can differ, so read the data plate.

Wire from the MCA, Breaker from the MOCP

Every central AC and heat pump condenser has two numbers on its data plate that decide the circuit: MCA (minimum circuit ampacity) sizes the conductor, and MOCP or "max fuse/breaker" (maximum overcurrent protection) sizes the breaker. The MCA already includes the 125% factor for the largest motor per NEC 440.32/440.33, so you do not add anything: pick the smallest wire whose 75°C ampacity is at least the MCA. The MOCP is usually larger than the MCA on purpose, because the breaker has to let the compressor inrush pass without tripping while still protecting the equipment (NEC 440.22).


Typical Central AC Wire Size by Tonnage

Rough starting ranges only. SEER rating, brand, and whether it is a heat pump all shift the MCA, so the nameplate always wins over this table.

Typical MCA, MOCP, and copper wire by central AC tonnage (nameplate governs)
Unit SizeTypical MCATypical MOCPCopper Wire
1.5 - 2 ton~15 - 18A~25A#14 - #12
2.5 - 3 ton~18 - 25A~30 - 35A#10
3.5 - 4 ton~25 - 30A~40 - 45A#8
5 ton~30 - 40A~50 - 60A#8 - #6

Wire at the 75°C column of NEC Table 310.16 sized to the MCA; ground per NEC 250.122. On a long run, check voltage drop. These are typical values, not code values: your unit's data plate carries the exact MCA and MOCP.


Size It to Your Nameplate

Enter your unit's MCA as the load to get the exact wire, or use the dedicated MCA/MOCP calculator to work from the compressor and fan data.

Loading calculator...

Working from the compressor RLA and fan FLA instead of a printed MCA? Use the MCA / MOCP calculator →


Frequently Asked Questions

What size wire do I need for a central air conditioner?

Size the wire to the unit's nameplate MCA (minimum circuit ampacity), not to the tonnage. The MCA is the minimum conductor ampacity the manufacturer requires, and it already includes the 125% factor for the largest motor (NEC 440.4, 440.32/440.33). Pick the smallest conductor whose 75C ampacity is at least the MCA. As a rough guide, a 2-3 ton unit runs an MCA around 15-25A, so #10 copper is common; a 4-5 ton unit can push the MCA to 25-40A and need #8 copper. Always read the data plate: two same-tonnage units can have different MCAs.

Is MCA or MOCP the wire size for an AC?

MCA sizes the wire; MOCP sizes the breaker. MCA (minimum circuit ampacity) is the smallest conductor ampacity allowed. MOCP (maximum overcurrent protective device, sometimes 'max fuse/breaker') is the largest breaker or fuse permitted, and you use a standard size at or below it. They are usually different numbers, and that is normal for AC: the breaker is intentionally larger than the wire's ampacity to let the compressor start (NEC 440 allows this because the MOCP protects the equipment, not just the wire).

Can I use the tonnage to size AC wire?

No, not reliably. Tonnage is cooling capacity, not electrical load, and two 3-ton units from different brands or SEER ratings can have noticeably different MCAs. The tonnage-based ranges you see online are rough starting points only. The nameplate MCA and MOCP are the code-required values, and an inspector sizes to them, so read the data plate on the condenser.

What size breaker for a central air conditioner?

Use a standard breaker at or below the nameplate MOCP (maximum overcurrent protection). If the MOCP is 35A and 35A is a standard size, use 35A; if the MOCP is a non-standard number, drop to the next standard size below it. Typical central AC MOCPs run 25-45A for 2-4 ton units. Never exceed the MOCP: it is the manufacturer's listed maximum.

Does a central AC need a disconnect and dedicated circuit?

Yes to both. A central AC or heat pump condenser must be on its own dedicated branch circuit (NEC 440.6/440.31), and a disconnecting means must be installed within sight of and readily accessible to the unit (NEC 440.14), which is the fused or non-fused pull-out box next to the condenser.


Related