NEC Article 440 (Air Conditioning)
What Size Wire for a Central Air Conditioner?
A central AC or heat pump is sized to the nameplate, not the tonnage. Here is how to read the MCA and MOCP, named models' figures by size, and the calculator to size your exact unit.
Wire from the MCA, Breaker from the MOCP
Every central AC and heat pump condenser has two numbers on its data plate that decide the circuit: MCA (minimum circuit ampacity) sizes the conductor, and MOCP or "max fuse/breaker" (maximum overcurrent protection) sizes the breaker. The MCA already includes the 125% factor for the largest motor per NEC 440.32/440.33, so you do not add anything: pick the smallest wire whose ampacity is at least the MCA, on the 60°C column of NEC Table 310.16, or the 75°C column where the breaker and the unit are listed and identified for 75°C conductors (NEC 110.14(C)(1)(a)). The MOCP is larger than the MCA on purpose (on 14 of the 14 named units below), because the breaker has to let the compressor inrush pass without tripping while still protecting the equipment (NEC 440.22).
Central AC Wire Size by Tonnage: Named Models
Each row is one condenser's MCA and MOCP as printed in Goodman's GLXS4B and Daikin's DX4SE spec sheets (208/230V single phase). The breaker is the largest standard size at or below the MOCP, and the copper is the smallest size on the 60°C column of NEC Table 310.16 that meets the MCA. Brand and model shift the MCA, so the nameplate wins over this table.
Named central AC condensers: the maker's MCA and MOCP, the breaker and code-minimum copper from them (nameplate governs)
Swipe the table sideways to see the rest of its columns. →
| Unit | Size | MCA | MOCP | Breaker | Copper (60°C) |
|---|---|---|---|---|---|
| Daikin DX4SEA1810A* | 1.5 ton | 11.9A | 20A | 20A | #14 |
| Goodman GLXS4BA1810A* | 1.5 ton | 10.9A | 15A | 15A | #14 |
| Daikin DX4SEA2410A* | 2 ton | 15.3A | 25A | 25A | #12 |
| Goodman GLXS4BA2410A* | 2 ton | 10.9A | 15A | 15A | #14 |
| Daikin DX4SEA3010A* | 2.5 ton | 17A | 25A | 25A | #12 |
| Goodman GLXS4BA3010A* | 2.5 ton | 15A | 25A | 25A | #14 |
| Daikin DX4SEA3610A* | 3 ton | 18.6A | 30A | 30A | #12 |
| Goodman GLXS4BA3610A* | 3 ton | 17.8A | 30A | 30A | #12 |
| Daikin DX4SEA4210A* | 3.5 ton | 23.4A | 40A | 40A | #10 |
| Goodman GLXS4BA4210A* | 3.5 ton | 19A | 30A | 30A | #12 |
| Daikin DX4SEA4810A* | 4 ton | 26.2A | 45A | 45A | #10 |
| Goodman GLXS4BA4810A* | 4 ton | 25.2A | 40A | 40A | #10 |
| Daikin DX4SEA6010A* | 5 ton | 32.4A | 50A | 50A | #8 |
| Goodman GLXS4BA6010A* | 5 ton | 32.4A | 50A | 50A | #8 |
The conductor has to carry the MCA where it is actually installed. Take its NEC Table 310.16 ampacity in the column matching the terminations (NEC 110.14(C)), correct it for the ambient (NEC 310.15(B)(1), plus the rooftop adder of NEC 310.15(B)(2) where the raceway sits in direct sun), adjust it for more than three current-carrying conductors (NEC Table 310.15(C)(1)), and compare THAT figure to the MCA. A conductor that clears the MCA on the printed table can be well under it on a hot roof or in a crowded raceway. Ground per NEC 250.122. On a long run, check voltage drop. Both spec sheets say “Always check the S&R plate for electrical data on the unit being installed”: your unit's data plate carries its exact MCA and MOCP.
Size It to Your Nameplate
It opens on the 30 A circuit of Goodman's and Daikin's 3 ton condensers. Enter your unit's MCA as the load and leave Continuous load off (the MCA already includes the 125%) to get the exact wire, or use the dedicated MCA/MOCP calculator to work from the compressor and fan data. The breaker line is a general-circuit value, not the maximum breaker (MOCP) on the data plate.
Working from the compressor RLA and fan FLA instead of a printed MCA? Use the MCA / MOCP calculator →
The code sections this page cites are named in the source receipt.
Frequently Asked Questions
What size wire do I need for a central air conditioner?
Size the wire to the unit's nameplate MCA (minimum circuit ampacity), not to the tonnage. The MCA is the minimum conductor ampacity the manufacturer requires, and it already includes the 125% factor for the largest motor (NEC 440.4, 440.32/440.33). Pick the smallest conductor whose ampacity on the 60C column of NEC Table 310.16 (the 75C column only where the breaker and the unit are listed and identified for 75C conductors, NEC 110.14(C)(1)(a)) is at least the MCA. Goodman's GLXS4B and Daikin's DX4SE 2 to 3 ton condensers list MCA 10.9 to 18.6A, which the 60C column meets with #14 to #12 copper; their 4 to 5 ton units list 25.2 to 32.4A, met with #10 to #8. Always read the data plate: two same-tonnage units can have different MCAs (the two 3 ton units list 17.8A and 18.6A).
Is MCA or MOCP the wire size for an AC?
MCA sizes the wire; MOCP sizes the breaker. MCA (minimum circuit ampacity) is the smallest conductor ampacity allowed. MOCP (maximum overcurrent protective device; Goodman's and Daikin's spec sheets print it as Max. Overcurrent Protection) is the largest breaker or fuse permitted, and you use a standard size at or below it. On every named unit in the table below they are different numbers, and that is normal for AC: the breaker is intentionally larger than the wire's ampacity to let the compressor start (NEC 440 allows this because the MOCP protects the equipment, not just the wire).
Can I use the tonnage to size AC wire?
No, not reliably. Tonnage is cooling capacity, not electrical load, and two units of one tonnage from different brands can list different MCAs: Goodman's and Daikin's 2 ton condensers list 10.9A and 15.3A, with maximum breakers of 15A and 25A. The nameplate MCA and MOCP are the code-required values, and an inspector sizes to them, so read the data plate on the condenser.
What size breaker for a central air conditioner?
Use a standard breaker at or below the nameplate MOCP (maximum overcurrent protection). If the MOCP is 35A and 35A is a standard size, use 35A; if the MOCP is a non-standard number, drop to the next standard size below it. Goodman's GLXS4B and Daikin's DX4SE 2 to 4 ton condensers list MOCPs of 15 to 45A, and both spec sheets call for time-delay fuses or HACR-type circuit breakers of that size. Never exceed the MOCP: it is the manufacturer's listed maximum.
Does a central AC need a disconnect and dedicated circuit?
A disconnect, yes: a disconnecting means must be installed within sight of and readily accessible to a central AC or heat pump condenser (NEC 440.14), which is the fused or non-fused pull-out box next to the condenser. A circuit to itself is not something Article 440 requires: NEC 440.22(B) sets the breaker where the compressor shares a circuit with other loads, so a dedicated circuit comes from the manufacturer's instructions where they call for one.
Does a central AC condenser need GFCI protection?
GFCI: at a dwelling, a central air conditioner's outdoor outlet falls under NEC 2023 210.8(F): "For dwellings, all outdoor outlets, other than those covered in 210.8(A), Exception No. 1, including outlets installed in the following locations, and supplied by single-phase branch circuits rated 150 volts or less to ground, 50 amperes or less, shall be provided with GFCI protection:" The listed-HVAC exception expired on September 1, 2026 in the NEC's own text, but some states deleted that expiry and some never had the exception at all; the outdoor HVAC GFCI check answers it by state.
Related
Can My Panel Handle It?
Before you add this load, the NEC 220.87 check on whether the service can carry it.
MCA / MOCP Calculator
Compute minimum circuit ampacity and max breaker from the compressor and fan data.
Wire Size for Appliances
Dryer, range, water heater, hot tub, and more: the circuit for each.
Wire Size Calculator
Size any load per NEC 310.16 with derating, then check voltage drop.
Superheat & Subcooling
Once it is wired, check the refrigerant charge with a PT-based diagnostic.