NEC 422.10 and the Manual
What Size Wire for a Tankless Water Heater?
An electric tankless heater is a large load, and a whole-house unit can be split across multiple circuits. Here are the makers' own circuits by model, when the NEC's 125% applies, and why the install manual has the last word.
Why It Is a Multi-Circuit Load
A whole-house electric tankless heater pulls far more current than a single practical residential circuit can carry: an 18 kW unit at 240V draws 75A. So makers divide the heater into equal element banks, each fed by its own double-pole breaker and conductor at the size the manual prints. EcoSmart's manual lists 2 breakers for its ECO 18, 3 for its ECO 27 and 4 for its ECO 36, each 40A with 8 AWG copper. Follow the manual's wiring chart exactly.
Tankless Water Heater Amperage & Wiring by kW
At 240V. Each row is a named model as its maker's manual or specification table prints it; your own unit's install manual is the reference the code requires you to follow (110.3(B)).
Total draw, circuit count and the maker's breaker per circuit by tankless model (240V), with the copper wire for that breaker at both termination columns
Swipe the table sideways to see the rest of its columns. →
| Unit Rating | Total Draw | Circuits | Per Circuit | Wire, Breaker (60°C terminations or NM-B) | Wire, Breaker (breaker and heater both marked 75°C) |
|---|---|---|---|---|---|
| Stiebel Eltron Mini 4-2, 3.5 kW at 220 to 240V (point of use) | 15A | 1 | 15A | #14 Cu, 15A (the maker's minimum recommended circuit breaker; 100% of load, per the maker) | |
| Stiebel Eltron DHC 3-2 Classic, 3.3 kW at 240V (point of use) | 14A | 1 | 14A | #14 Cu, 15A (the maker's minimum recommended circuit breaker; 100% of load, per the maker) | |
| Stiebel Eltron DHC 6-2 Classic, 6.0 kW at 240V (point of use) | 25A | 1 | 25A | #10 Cu, 25A (the maker's minimum recommended circuit breaker, up to 30A per its specification sheet; 100% of load, per the maker) | |
| Rheem RTEX-04T, 3.5 kW at 120V (point of use) | 29A | 1 | 29A | #10 Cu, 30A (the maker's single-pole breaker; NEC intermittent duty, per the maker) | |
| Rheem RTEX-06T, 6.5 kW at 240V (point of use) | 27A | 1 | 27A | #10 Cu, 30A (the maker's double-pole breaker; NEC intermittent duty, per the maker) | |
| Bosch Tronic 3000 US4-2R, 3,781 to 4,500 W at 208 to 240V (point of use) | 20A | 1 | 20A | #10 Cu, 30A (the maker's fuse protection) | |
| Bosch Tronic 3000 US7-2R, 6,050 to 7,200 W at 208 to 240V (point of use) | 30A | 1 | 30A | #10 Cu, 30A (the maker's fuse protection) | |
| Stiebel Eltron Tempra 12 B, 12 kW | 50A | 1 | 50A breaker (minimum recommended) | #6 Cu, 50A | #8 Cu, 50A |
| Stiebel Eltron Tempra 15 B, 14.4 kW | 60A | 2 | 30A breaker (minimum recommended) | #10 Cu, 30A | #10 Cu, 30A |
| Stiebel Eltron Tempra 20 B, 19.2 kW | 80A | 2 | 40A breaker (minimum recommended) | #8 Cu, 40A | #8 Cu, 40A |
| Stiebel Eltron Tempra 24 B, 24 kW | 100A | 2 | 50A breaker (minimum recommended) | #6 Cu, 50A | #8 Cu, 50A |
| Stiebel Eltron Tempra 29 B, 28.8 kW | 120A | 3 | 40A breaker (minimum recommended) | #8 Cu, 40A | #8 Cu, 40A |
| Stiebel Eltron Tempra 36 B, 36 kW | 150A | 3 | 50A breaker (minimum recommended) | #6 Cu, 50A | #8 Cu, 50A |
| EcoSmart ECO 18, 18 kW | 75A | 2 | 40A breaker (required) | #8 Cu, 40A | #8 Cu, 40A |
| EcoSmart ECO 24, 24 kW | 100A | 3 | 40A breaker (required) | #8 Cu, 40A | #8 Cu, 40A |
| EcoSmart ECO 27, 27 kW | 112.5A | 3 | 40A breaker (required) | #8 Cu, 40A | #8 Cu, 40A |
| EcoSmart ECO 36, 36 kW | 150A | 4 | 40A breaker (required) | #8 Cu, 40A | #8 Cu, 40A |
| Rheem RETEX-13, 13 kW | 54A | 1 | 60A breaker (recommended) | #4 Cu, 60A | #6 Cu, 60A |
| Rheem RETEX-18, 18 kW | 75A | 2 | 40A breaker (recommended) | #8 Cu, 40A | #8 Cu, 40A |
| Rheem RETEX-27, 27 kW | 113A | 3 | 40A breaker (recommended) | #8 Cu, 40A | #8 Cu, 40A |
The total, the circuit count and the breaker per circuit are each maker's printed figures (Stiebel Eltron prints a per-circuit load, so its total is that times the circuits). The wire is this site's wire-size engine's copper conductor for the maker's breaker from NEC Table 310.16 (240.4(D) for the small sizes), and the maker's minimum where that is larger; ground per 250.122. The right-hand column is the 75°C column, which on a circuit of 100A or less holds only where the breaker and the equipment are both listed and identified for 75°C conductors (NEC 110.14(C)(1)(a)(3)); unmarked terminations and NM-B cable (NEC 334.80) take the 60°C column. The install manual's chart governs.
The NEC 2023 sizes a branch circuit at 125% for a continuous load, a load whose maximum current is expected to continue for 3 hours or more (Article 100; 210.19(A)(1), 210.20(A) and 422.10(A)(3)); Article 422's 125% rule for water heaters names storage-type water heaters, not a tankless unit. Stiebel Eltron's Tempra manual notes “This is our recommendation for overcurrent protection sized at 100% of load. Check local codes for compliance if necessary.”; its DHC Classic manual adds “Overcurrent protection sized at 100% of load (DP for 240/208/277 V & SP for 120 V models). Tankless water heaters are considered a non-continuous load.”; Rheem's point-of-use manual labels its breaker “Required minimum breaker size (per NEC-Intermittent Duty)”. A circuit sized at 125% instead can call for a larger breaker than the maker prints. Where the unit is marked with a protective device rating, the breaker may not exceed it (422.11(A)), and the unit is installed per its instructions (110.3(B)).
Size a Single Circuit
It opens on the 40 A circuit of an 18 kW unit, sized to that breaker. For your unit, enter one circuit's breaker size from the install manual as the load and leave Continuous load off; if you enter the manual's per-circuit current instead, leave Continuous load off for the makers' 100% sizing, or turn Continuous load on where the load is continuous (3 hours or more) for the 125%, and check the breaker it gives against the manual's and the rating marked on the unit (422.11(A)).
Not sure the panel can take it? Run a dwelling load calculation →
The code sections this page cites are named in the source receipt.
Frequently Asked Questions
What size wire do I need for an electric tankless water heater?
It depends on the model, and a whole-house unit can need more than one circuit; its manual prints the breaker and wire for each. EcoSmart's ECO 18 (18 kW, 75A) lists 2 x 40A breakers with 8 AWG copper, so 2 circuits of #8 Cu; Stiebel Eltron's Tempra 24 B (24 kW, 100A) lists 2 x 50A breakers with 8 AWG copper, so 2 circuits of #6 Cu (#8 Cu only on 75°C-marked terminations); Rheem's RETEX-27 (27 kW, 113A) lists 3 x 40A breakers with 8 AWG copper, so 3 circuits of #8 Cu. Each conductor here is this site's engine's copper size for the maker's breaker, never smaller than the maker's minimum. The NEC 2023 sizes a branch circuit at 125% for a continuous load, a load whose maximum current is expected to continue for 3 hours or more (Article 100; 210.19(A)(1), 210.20(A) and 422.10(A)(3)); Article 422's 125% rule for water heaters names storage-type water heaters, not a tankless unit. Stiebel Eltron's Tempra table sizes its breakers at 100% of load, and Rheem and EcoSmart print fixed breakers; sized at 125% instead, a circuit can call for a larger breaker than the manual lists. Where the unit is marked with a protective device rating, the breaker may not exceed it (422.11(A)), and the unit is installed per its instructions (110.3(B)). A point-of-use unit takes one circuit at the breaker and wire its manual prints: Stiebel Eltron's DHC 6-2 Classic (6.0 kW at 240V) lists 25A (minimum recommended circuit breaker) and 10 AWG copper, and Rheem's RTEX-06T (6.5 kW at 240V) lists 30A (double-pole breaker) and 10 AWG copper (more models in the point-of-use question below). The install manual specifies the exact number of circuits and the breaker size for each, and it governs.
How many amps does a tankless water heater use?
Divide the kilowatts by the voltage: an 18 kW unit at 240V draws 75A (18,000 / 240), a 24 kW unit draws 100A, and a 27 kW unit draws 112.5A. EcoSmart's manual prints the same draws for its ECO 18, ECO 24 and ECO 27: 75, 100 and 112.5 amps. Whether the circuit is then sized at 125% turns on the NEC's continuous-load definition, a maximum current expected to continue for 3 hours or more (Article 100); Stiebel Eltron's DHC Classic and Mini manuals call tankless water heaters a non-continuous load. A load that size is why a whole-house unit is split across multiple breakers, and why it needs a service-capacity check before you add one.
Why does a tankless water heater need multiple breakers?
Because the total current exceeds what a single practical residential circuit and conductor can carry. Rather than run one very large feeder, makers split the load into equal double-pole circuits, each with its own breaker and conductor at the size the manual's chart prints: EcoSmart's ECO 36 (36 kW, 150A) lists 4 x 40A breakers with 8 AWG copper, so 4 circuits of #8 Cu; Stiebel Eltron's Tempra 36 B (36 kW, 150A) lists 3 x 50A breakers with 8 AWG copper, so 3 circuits of #6 Cu (#8 Cu only on 75°C-marked terminations). This keeps the wire at a manageable gauge per circuit and matches the heater's internal element banks. Wire each circuit exactly as the manual's chart specifies.
Will my electrical panel handle a tankless water heater?
Not without a check. An electric tankless adds a large load, so on a 100A or 150A service it calls for a load calculation and can force a service upgrade. Run a dwelling load calculation (NEC 220.83) including the tankless draw before committing. A gas tankless avoids this entirely, needing only a small 120V circuit for the controls and igniter.
What size wire for a point-of-use tankless heater?
The circuit is the one the unit's own installation manual prints, and the manual governs. Stiebel Eltron's Mini Series Electric Tankless Water Heaters manual lists the Mini 4-2 at 3.5 kW at 220 to 240V, 15A, 15A (minimum recommended circuit breaker) and 14 AWG copper (page 17); Stiebel Eltron's DHC Classic Operation and Installation manual lists the DHC 3-2 Classic at 3.3 kW at 240V, 14A, 15A (minimum recommended circuit breaker) and 14 AWG copper (page 11); Stiebel Eltron's DHC Classic Operation and Installation manual lists the DHC 6-2 Classic at 6.0 kW at 240V, 25A, 25A (minimum recommended circuit breaker) and 10 AWG copper (page 12), and its specification sheet adds “25 A breaker may be sized up to 30 A.”; Rheem's tankless electric Use & Care Manual (3.5 kW and 6.5 kW) lists the RTEX-04T at 3.5 kW at 120V, 29A, 30A (single-pole breaker) and 10 AWG copper (pages 5 and 8); Rheem's tankless electric Use & Care Manual (3.5 kW and 6.5 kW) lists the RTEX-06T at 6.5 kW at 240V, 27A, 30A (double-pole breaker) and 10 AWG copper (pages 5 and 8); Bosch's Tronic 3000 Installation Manual and Operating Instructions (6 721 803 545, 2020/02) lists the Tronic 3000 US4-2R at 3,781 to 4,500 W at 208 to 240V, 20A, 30A (fuse protection) and 10 AWG copper (pages 7 and 9); Bosch's Tronic 3000 Installation Manual and Operating Instructions (6 721 803 545, 2020/02) lists the Tronic 3000 US7-2R at 6,050 to 7,200 W at 208 to 240V, 30A, 30A (fuse protection) and 10 AWG copper (pages 7 and 9). Two of these makers state the basis of their breaker, and neither is 125%: Stiebel Eltron's tables note “Overcurrent protection sized at 100% of load (DP for 240/208/277 V & SP for 120 V models). Tankless water heaters are considered a non-continuous load.”, and Rheem's table labels its breaker “Required minimum breaker size (per NEC-Intermittent Duty)”. The NEC 2023 sizes a branch circuit at 125% for a continuous load, a load whose maximum current is expected to continue for 3 hours or more (Article 100; 210.19(A)(1), 210.20(A) and 422.10(A)(3)); Article 422's 125% rule for water heaters names storage-type water heaters, not a tankless unit. If your inspector treats the unit as continuous, size it at 125% in the calculator below; at 125% a unit can call for a larger breaker than its maker lists. Where the unit is marked with a protective device rating, the breaker may not exceed it (422.11(A)), and the unit is installed per its instructions (110.3(B)), so where 125% calls for more than the unit's marked or printed breaker, ask the maker before you install. The nameplate states the unit's own rating. Whole-house units are the multi-circuit case above.
Related
Can My Panel Handle It?
Before you add this load, the NEC 220.87 check on whether the service can carry it.
Storage Water Heater Wire Size
A standard tank unit is the simple case: one 30A / #10 circuit.
Dwelling Load Calculator
Check whether your service can carry the added tankless load (NEC 220).
Wire Size for Appliances
Dryer, range, water heater, hot tub, and more: the circuit for each.
Wire Size Calculator
Size any circuit per NEC 310.16 with continuous-load and derating.