NEC Article 430 (Motors)
What Size Wire for an Air Compressor?
It comes down to plug-in versus hardwired. A small 120V portable uses an existing circuit; a stationary 240V shop compressor is a motor load sized by NEC Article 430. Here are both, with the tables and the calculator.
Plug-In or Hardwired Decides Everything
A cord-and-plug compressor is not a circuit you design: you plug it into an existing branch circuit, and the circuit breaker plus the motor's built-in thermal overload protect it (NEC 430.32 covers motor running-overload protection). Give it a dedicated 20A receptacle if you can, because the starting inrush trips shared circuits. A hardwired stationary compressor is a full motor branch circuit under Article 430: the conductor carries 125% of the table full-load current (430.22) and the breaker may be as large as 250% of it (430.52) to let the motor start. The wire ends up small and the breaker large on purpose; a separate overload device (430.32), not the breaker, protects the conductor.
Hardwired 120V Compressor (Small)
Single-phase 120V motor, copper. FLC from NEC Table 430.248. A cord-and-plug 120V portable plugs into a receptacle circuit.
Swipe the table sideways to see the rest of its columns. →
| Motor HP | FLC (430.248) | Min Wire (430.22) | Max Breaker (430.52) | Ground |
|---|---|---|---|---|
| 1/2 HP | 9.8 A | #14 | 25 A | #10 |
| 3/4 HP | 13.8 A | #12 | 35 A | #10 |
| 1 HP | 16 A | #12 | 40 A | #10 |
| 1-1/2 HP | 20 A | #10 | 50 A | #10 |
A larger compressor can be built for 240V, because the 120V full-load current gets high enough to need heavy wire and a large breaker.
On several rows the ground is larger than the circuit conductor, and on a motor circuit that is expected: NEC 430.52 sizes the breaker for locked-rotor inrush at up to 250 percent of full-load current while 430.22 sizes the conductor at 125 percent, and Table 250.122 sizes the ground from the breaker. We publish the table minimum. NEC 250.122(A) also says the grounding conductor is “not required to be larger than the circuit conductors supplying the equipment”, and that is read by some inspectors as permitting the smaller conductor on exactly these rows. It is a defensible reading and we do not publish it as the answer, because a ground larger than the table is never a violation and a ground smaller than it may be. Ask your AHJ before downsizing.
Hardwired 240V Compressor (Shop)
Single-phase 240V motor, copper. FLC from NEC Table 430.248.
Swipe the table sideways to see the rest of its columns. →
| Motor HP | FLC (430.248) | Min Wire (430.22) | Max Breaker (430.52) | Ground |
|---|---|---|---|---|
| 1 HP | 8 A | #14 | 20 A | #12 |
| 1-1/2 HP | 10 A | #14 | 25 A | #10 |
| 2 HP | 12 A | #14 | 30 A | #10 |
| 3 HP | 17 A | #10 | 45 A | #10 |
| 5 HP | 28 A | #8 | 70 A | #8 |
“Min Wire” is the code minimum by ampacity (60°C column); the next size up adds margin for voltage drop. The breaker shown is the maximum inverse-time size; a smaller standard breaker is fine if it reliably starts the motor.
On several rows the ground is larger than the circuit conductor, and on a motor circuit that is expected: NEC 430.52 sizes the breaker for locked-rotor inrush at up to 250 percent of full-load current while 430.22 sizes the conductor at 125 percent, and Table 250.122 sizes the ground from the breaker. We publish the table minimum. NEC 250.122(A) also says the grounding conductor is “not required to be larger than the circuit conductors supplying the equipment”, and that is read by some inspectors as permitting the smaller conductor on exactly these rows. It is a defensible reading and we do not publish it as the answer, because a ground larger than the table is never a violation and a ground smaller than it may be. Ask your AHJ before downsizing.
Size Your Exact Compressor
It opens on the 30 A circuit of a 2 HP compressor, sized as a general circuit, which gives a conductor at or above the NEC 430.22 motor minimum in the table above. For your unit, enter the Table 430.248 full-load current for its horsepower (the FLC column above), or the nameplate full-load current if the unit is marked with both horsepower and full-load current, and turn Continuous load on: it applies the 125% NEC 430.22 requires. The breaker line is a general-circuit value, not the NEC 430.52 motor breaker. For a long run, the result links to the voltage drop calculator, which checks that wire over your run; this tool does not size for voltage drop.
The code sections this page cites are named in the source receipt.
Frequently Asked Questions
What size wire and breaker for an air compressor?
It depends on whether it plugs in or is hardwired. A small 120V portable or pancake compressor (up to about 1.5 running HP) is cord-and-plug, so you do not design a circuit for it: plug it into an existing 15A or 20A branch circuit, and the branch breaker plus the compressor's built-in thermal overload protect it (NEC 430.32). A hardwired stationary shop compressor is a motor load under NEC Article 430: the conductor carries 125% of the table full-load current (430.22) and an inverse-time breaker may be up to 250% of it (430.52). A 2 HP 240V unit lands on a 30A breaker; a 5 HP 240V unit on 70A with #8 copper.
Should I size the compressor circuit from the advertised horsepower?
No. Air compressor horsepower can be overstated: a 'peak' or 'developed' 5 HP marketing figure can map to a 2-3 running-HP motor that draws far less. Size the circuit from the nameplate running amps (or the true rated HP), never the peak HP on the box. The NEC uses the table full-load current for the motor's actual rated horsepower, so if the running amps and the advertised HP disagree, the nameplate amps win.
Can I plug a compressor into a regular outlet?
Yes for a small 120V unit, with two cautions. First, a compressor draws heavy starting current, so it should be the only significant load on that circuit and ideally on its own 20A receptacle; running it on a shared 15A kitchen or lighting circuit invites nuisance trips. Second, a long or undersized extension cord causes voltage drop that overheats the motor, so use a short, heavy-gauge cord (or none). Larger 240V compressors are hardwired or use a dedicated NEMA 6-20/6-30/6-50 receptacle sized to the circuit.
Does an air compressor circuit need GFCI protection?
GFCI: plugged into a receptacle in a dwelling location NEC 2023 210.8(A) lists (210.8(A)(2) "Garages and also accessory buildings that have a floor located at or below grade level not intended as habitable rooms and limited to storage areas, work areas, and areas of similar use"), an air compressor needs GFCI protection; 210.8(A) reaches 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground. Hardwired, it has no receptacle for 210.8(A) to reach, and 2023 210.8(D)'s list does not name it. Which edition applies is the one your jurisdiction has adopted.
Why can a compressor breaker be larger than the wire's rating?
Because a motor circuit protects the wire and provides starting headroom with two different devices. The branch-circuit breaker (NEC 430.52) is sized up to 250% of the motor's full-load current so it does not trip on the inrush at startup; it only handles short circuits and ground faults. The conductor is protected from overload by a separate overload device set at 115-125% of the nameplate FLA (430.32), which on a compressor can be the built-in motor thermal protector or pressure-switch overload. NEC 240.4(G) exempts motor conductors from the small-conductor breaker limits, so a small wire on a large motor breaker is code-correct.
Related
Can My Panel Handle It?
Before you add this load, the NEC 220.87 check on whether the service can carry it.
Well Pump Wire Size
Another single-phase motor load, with the voltage-drop upsizing over the well depth.
Pool Pump Wire Size
Motor sizing plus the NEC 680 GFCI and equipotential bonding rules.
Wire Size for Appliances
Dryer, range, water heater, AC, and more: the circuit for each.
Wire Size Calculator
Size any load per NEC 310.16 with derating, then check voltage drop.