NEC Article 430 (Motors)
What Size Wire for an Air Compressor?
It comes down to plug-in versus hardwired. A small 120V portable uses an existing circuit; a stationary 240V shop compressor is a motor load sized by NEC Article 430. Here are both, with the tables and the calculator.
Plug-In or Hardwired Decides Everything
A cord-and-plug compressor is not a circuit you design: you plug it into an existing branch circuit, and the circuit breaker plus the motor's built-in thermal overload protect it (NEC 430.32(C) covers automatically-started, cord-and-plug motors). Give it a dedicated 20A receptacle if you can, because the starting inrush trips shared circuits. A hardwired stationary compressor is a full motor branch circuit under Article 430: the conductor carries 125% of the table full-load current (430.22) and the breaker may be as large as 250% of it (430.52) to let the motor start. The wire ends up small and the breaker large on purpose; a separate overload device (430.32), not the breaker, protects the conductor.
Hardwired 120V Compressor (Small)
| Motor HP | FLC (430.248) | Min Wire (430.22) | Max Breaker (430.52) | Ground |
|---|---|---|---|---|
| 1/2 HP | 9.8 A | #14 | 25 A | #14 |
| 3/4 HP | 13.8 A | #12 | 35 A | #12 |
| 1 HP | 16 A | #12 | 40 A | #12 |
| 1-1/2 HP | 20 A | #10 | 50 A | #10 |
Above about 1.5 HP a compressor is normally 240V, because the 120V full-load current gets high enough to need heavy wire and a large breaker.
Hardwired 240V Compressor (Shop)
| Motor HP | FLC (430.248) | Min Wire (430.22) | Max Breaker (430.52) | Ground |
|---|---|---|---|---|
| 1 HP | 8 A | #14 | 20 A | #14 |
| 1-1/2 HP | 10 A | #14 | 25 A | #14 |
| 2 HP | 12 A | #14 | 30 A | #14 |
| 3 HP | 17 A | #10 | 45 A | #10 |
| 5 HP | 28 A | #8 | 70 A | #8 |
“Min Wire” is the code minimum by ampacity (60°C column); many installers run the next size up for margin and voltage drop. The breaker shown is the maximuminverse-time size; a smaller standard breaker is fine if it reliably starts the motor.
Size Your Exact Compressor
Enter the nameplate running amps as the load (use 125% of it for the conductor), and add your run length to check voltage drop.
Frequently Asked Questions
What size wire and breaker for an air compressor?
It depends on whether it plugs in or is hardwired. A small 120V portable or pancake compressor (up to about 1.5 running HP) is cord-and-plug, so you do not design a circuit for it: plug it into an existing 15A or 20A branch circuit, and the branch breaker plus the compressor's built-in thermal overload protect it (NEC 430.32(C)). A hardwired stationary shop compressor is a motor load under NEC Article 430: the conductor carries 125% of the table full-load current (430.22) and an inverse-time breaker may be up to 250% of it (430.52). A 2 HP 240V unit lands on a 30A breaker; a 5 HP 240V unit on 70A with #8 copper.
Should I size the compressor circuit from the advertised horsepower?
No. Air compressor horsepower is notoriously overstated: a 'peak' or 'developed' 5 HP marketing figure often maps to a 2-3 running-HP motor that draws far less. Size the circuit from the nameplate running amps (or the true rated HP), never the peak HP on the box. The NEC uses the table full-load current for the motor's actual rated horsepower, so if the running amps and the advertised HP disagree, the nameplate amps win.
Can I plug a compressor into a regular outlet?
Usually yes for a small 120V unit, with two cautions. First, a compressor draws heavy starting current, so it should be the only significant load on that circuit and ideally on its own 20A receptacle; running it on a shared 15A kitchen or lighting circuit invites nuisance trips. Second, a long or undersized extension cord causes voltage drop that overheats the motor, so use a short, heavy-gauge cord (or none). Larger 240V compressors are hardwired or use a dedicated NEMA 6-20/6-30/6-50 receptacle sized to the circuit.
Why can a compressor breaker be larger than the wire's rating?
Because a motor circuit protects the wire and provides starting headroom with two different devices. The branch-circuit breaker (NEC 430.52) is sized up to 250% of the motor's full-load current so it does not trip on the inrush at startup; it only handles short circuits and ground faults. The conductor is protected from overload by a separate overload device set at 115-125% of the nameplate FLA (430.32), which on most compressors is the built-in motor thermal protector or pressure-switch overload. NEC 240.4(G) exempts motor conductors from the small-conductor breaker limits, so a small wire on a large motor breaker is code-correct.
Related
Well Pump Wire Size
Another single-phase motor load, with the voltage-drop upsizing over the well depth.
Pool Pump Wire Size
Motor sizing plus the NEC 680 GFCI and equipotential bonding rules.
Wire Size for Appliances
Dryer, range, water heater, AC, and more: the circuit for each.
Wire Size Calculator
Size any load per NEC 310.16 with derating and voltage drop.