Electrical / runnable MCP tool
Run the Biggest EV Charger Calculator (NEC 220.87 + EVEMS) in your AI assistant
Through the free Intry MCP server, Claude, ChatGPT, or Cursor runs this exact calculator and hands back a verdict and the cited source, not a guess. Tool name: max_ev_charger.
What you get back: the largest standard EVSE output that fits, plus the branch wire, breaker and ground. The added charger enters the 220.87 service check at 100% of its 220.57 value, so the fit is the service headroom divided by the voltage, floored to a standard rating; the 125% continuous factor sizes only its branch.
How it computes the answer
Computed from the NEC 220.87 inverse solve against your metered demand, with the EVEMS relaxing only the service calc (220.70 / 625.42(A) / 750.30); the branch is always 125% of the full charger output (210.20(A) / 625.41) on NEC Table 310.16 (75°C only on terminations marked for it, 110.14(C)(1)(a)(3)) with the 240.6(A) breaker and Table 250.122 ground.
What it cites
Your assistant calls the same engine the interactive calculator calls, with the inputs listed under Inputs. These are the sources that engine reads.
- NEC 220.87
- Existing-dwelling load method, run in reverse: your metered maximum demand at 125% sets the headroom, and the biggest charger is the amps left before the service rating is reached. The added charger enters the service check at 100% of its rating (its 220.57 value, no demand factor). NFPA 70-2023, p. 70-100.
- NEC 220.70
- Energy management systems, new in the 2023 NEC: an EMS-controlled maximum (the device setpoint) may be used as a single continuous value in the feeder and service load calculation. This is what lets a shed or throttle device relax the SERVICE calc without a panel upgrade.
- NEC 625.42 and 750.30
- EV charging is a continuous load (625.42). An external EMS relaxes only the service and feeder calculation (625.42(A) / 750.30), never a single charger's branch; the EVSE's own restricted-access adjusted setting under 625.42(B) is the route this tool recognizes for a smaller branch, and it is not one this tool takes: every condition 625.42(B) attaches, under 750.30(C) and the manufacturer's instructions, is a fact about installed equipment. The tools name the rule and size from the full rating.
- NEC 210.20(A) and 625.41
- The branch overcurrent device and conductor are sized at 125% of the FULL EVSE hardware output, always, for every external device type. An external shed or throttle does not change the EVSE's rating, so the branch is protected to what the unit can pull if the device fails or is bypassed.
- NEC Table 310.16
- Conductor ampacity for the branch, the general ampacity table for conductors in raceway or cable, read at the 75C column with the 110.14(C) terminal cap. The branch routes through the locked wire-size engine. Read from the primary (p.70-187).
- NEC 110.14(C)(1)(a)(3) and 334.80
- When the 75C column holds. On a circuit rated 100 amperes or less, 110.14(C)(1)(a) allows the 75C column under (3), "Conductors with higher temperature ratings if the equipment is listed and identified for use with such conductors" (NFPA 70-2023, p. 70-65), and 334.80 holds NM-B cable to the 60C column. So where the branch this tool names holds only at 75C, the answer says so beside the conductor. Whether your breaker and charger are marked for 75C conductors is a fact on the equipment, not something this tool can see.
- NEC 240.6(A), 240.4(D), and Table 250.122
- Standard overcurrent-device ratings (240.6(A)), the small-conductor cap on #14/#12/#10 (240.4(D)), and the equipment grounding conductor sized from the overcurrent device (Table 250.122). Read from the primary: 240.6(A) on p. 70-124, 240.4(D) on p. 70-123, Table 250.122 on p. 70-158.
- NEC 750.30(C)(1) through (C)(4), and 750.50
- The four conditions on using an EMS to limit current, stated by the code in the order the code states them. 750.30(C)(1) permits a single current setpoint equal to the system's maximum ampere setting, and names that same value as the one 220.70 allows in the connected-load calculation, which is why the two citations travel together in this tool. 750.30(C)(2) requires the system to use monitoring and controls that cease current flow automatically when the EMS malfunctions. 750.30(C)(3) permits adjustable settings only where access is restricted by one of five means: behind a removable and sealable cover, behind a cover or door needing a tool, behind locked doors reachable only by qualified personnel, password protected with the password held by qualified personnel only, or software whose access to the adjusting means is password protected for qualified personnel only. 750.30(C)(4) requires the equipment supplying the branch circuit, feeder or service to be field marked with the maximum current setting, the date of calculation and setting, the loads and sources tied to the current-limiting feature, and wording that the setting is not to be bypassed, marked per 110.21(B) and visible before servicing. 750.50 adds a directory of the controlled devices and circuits, posted on the controller, disconnect or branch-circuit overcurrent device. Not one of these is visible to a calculator, so this tool names them as site conditions and sizes the branch from the full charger output regardless. Read from the printed primary at pages 70-668 and 70-669 on 2026-08-23.
- NEC 220.60
- Noncoincident loads, NFPA 70-2023, p. 70-96: "If it is unlikely that two or more noncoincident loads will be in use simultaneously, using only the largest load(s) that will be used at one time for calculating the total load of a feeder or service shall be permitted." This is the section a circuit-share switch actually works under. It is why this tool's answer for that device type cites 220.60 and 220.57 and NOT 625.42(A), 220.70 or 750.30: time-sharing one existing branch invokes no service relaxation, and saying otherwise would attribute a branch-interlock answer to sections written about a service and a feeder.
- NEC 210.20(A)
- Branch-circuit overcurrent protection at 125 percent of a continuous load, p. 70-84. This is the rule behind the sentence this tool repeats on every path: the branch is always sized to the FULL charger output at 125 percent, whatever an energy management system does to the service calculation. 220.70 speaks of limiting current to a feeder or service, not to a branch, which is the same split as 625.42(A) against (B).
- NEC 230.90 and NEC 240.4
- Named where this tool tells you a feeder or service still needs its own overcurrent protection. NFPA 70-2023, p. 70-115, 230.90(A): "Such protection shall be provided by an overcurrent device in series with each ungrounded service conductor that has a rating or setting not higher than the ampacity of the conductor." NEC 240.4 is the general conductor rule on the feeder side, p. 70-122 for the lead-in and (A), with 240.4(D) on p. 70-123. Neither is computed here; the tool names the requirement and stops.
- NEC 110.3(B)
- Equipment must be installed and used in accordance with its listing and labeling, which is why a manufacturer's instruction outranks a generic code minimum in this tool. It is the section behind the refusal that fires when a restricted-access adjusted rating is entered: NEC 625.42(B) permits an EVSE to be rated at that setting, but this tool accepts the value without applying it, says so in those words, and leaves the listed equipment's own instructions governing.
- The load management devices' own documents
- RVE, DCC Electric Vehicle Energy Management System (read 2026-07-11): https://rve-usa.com/documentation-installation-manual-dcc-10-gen3/. Emporia Energy, Emporia EV Charger with PowerSmart load management (read 2026-07-11): https://www.emporiaenergy.com/pro-ev-charger/. Wallbox, Wallbox Pulsar Plus with Power Boost (read 2026-07-11): https://wallbox.com/en_us/pulsar-plus-ev-charger. Splitvolt, Splitvolt Splitter Switch (read 2026-10-18 · a retailer's copy, on the document host of Amazon): https://m.media-amazon.com/images/I/A18gEUkPMbL.pdf
- NEC 750.6, 750.30, and 750.50, energy management systems
- What an energy management system must be, and what it is not permitted to do. 750.6 requires the system to be listed, as a complete system, as a kit for field installation in switch or overcurrent-device enclosures, or as listed individual components assembled as a system. 750.30 permits an EMS to monitor and control loads and sources, and then bounds it: under 750.30(A) it may not override the load-shedding controls that hold minimum capacity for fire pumps, emergency systems, legally required standby systems and critical operations power systems, and under 750.30(B) it may not disconnect power to elevators, to positive mechanical ventilation for hazardous locations, to ventilation exhausting hazardous gas, to circuits supplying emergency lighting, or to essential electrical systems in health care facilities. 750.30(C) states plainly that an EMS shall not cause a branch circuit, feeder or service to be overloaded, and where one is used to limit current on a conductor it attaches four conditions: a single current setpoint, which is also the value 220.70 permits in the load calculation; monitoring and controls that cease current flow automatically on malfunction; adjustable settings reachable only by one of the five means 750.30(C)(3) names (a sealable cover, a tool-opened cover or door, a locked door, a password held by qualified personnel only, or software whose password-protected access is for qualified personnel only); and field marking of the equipment with the maximum current setting, the date of calculation, the loads and sources involved, and wording that the current-limiting feature is not to be bypassed. 750.50 additionally requires a directory identifying the controlled devices and circuits, posted on the controller, disconnect or branch-circuit overcurrent device. These are site facts about installed equipment, so this tool names them and does not treat any of them as satisfied. Read from the printed primary at pages 70-668 and 70-669 on 2026-08-23.
- NEC 230.79 and NEC 230.42(A)(1)
- Two service rules that size DIFFERENT quantities, and this tool keeps them apart on purpose. NFPA 70-2023, p. 70-113: "230.79 Rating of Service Disconnecting Means. The service disconnecting means shall have a rating not less than the calculated load to be carried, determined in accordance with Part III, IV, or V of Article 220, as applicable." That is the SERVICE RATING, set from the Article 220 calculated load at 100 percent, and it is the quantity the panel check in this tool compares against. NFPA 70-2023, p. 70-110: 230.42(A)(1) sizes SERVICE-ENTRANCE CONDUCTORS at "the sum of the noncontinuous loads plus 125 percent of continuous loads". This tool does not size service conductors and never applies that 125 percent to the service rating. Reading 230.42(A)(1) without reading 230.79 beside it is how a continuous designation gets applied to the wrong quantity.
- NEC 625.42(B) + 750.30(C) + 110.3(B)
- The adjusted-setting route. NEC 625.42 sizes the service and feeder from the product ratings unless the installation's overall rating is limited through controls permitted by 625.42(A) or (B), and of those two only (B) changes what an EVSE's own ampere rating IS, which is the quantity 625.41 sizes the branch overcurrent device from. So an EVSE's restricted-access adjusted current setting is the route 625.42 gives to that unit's own rating being smaller, and this tool never takes it: nothing in this tool is sized from a setting you enter. The conductor, breaker, ground and voltage drop come from the full hardware rating, and the panel check from the greater of that load and NEC 220.57's 7,200 VA minimum. A setting you enter is echoed back with the conditions rather than applied. Those conditions are facts about installed equipment that a calculator cannot check, and there are 4 of them: Where the adjusting means is part of an energy management system, that system uses monitoring and controls to automatically cease current flow if it malfunctions. 750.30(C) applies its subdivisions where an EMS is used to limit the current on a conductor. (NEC 750.30(C)(2)) Access to the ampere adjusting means is restricted by at least one of the five means 750.30(C)(3) names: behind a removable and sealable cover over the adjustment, behind a cover or door that needs a tool to open, behind a locked door accessible only to qualified personnel, password protected with the password held by qualified personnel only, or software whose access to the adjusting means is password protected for qualified personnel only. (NEC 750.30(C)(3)) The equipment supplying the branch circuit is field marked with the maximum current setting, the date of the calculation and setting, identification of the loads and sources associated with the current limiting feature, and the words "The setting for the EMS current limiting feature shall not be bypassed". Those markings meet the requirements in 110.21(B) and are located so they are clearly visible to qualified persons before examination, adjustment, servicing, or maintenance of the equipment. (NEC 750.30(C)(4)) The adjustment was made in accordance with the manufacturer's instructions, and the adjusted rating appears on the rating label with enough durability to withstand the environment involved. (NEC 625.42(B) / 110.3(B)) They are the conditions this tool can name, not a full compliance checklist: 625.40, 625.54 and 750.30's own capacity requirement are untouched by them. NFPA 70-2023, pp. 70-557 (625.42) and 70-668 to 70-669 (750.30(C)).
- NEC 700.4(C)(1), informational note
- Where the code uses the words peak load shaving: an informational note to 700.4(C)(1), which permits an emergency source to run in parallel with the normal source, reads "Peak load shaving is one application for parallel source operation" (NFPA 70-2023, p. 70-626). That describes a source running in parallel with the supply, not a device that limits load, so this tool reads an EV energy management system under 625.42 and 750.30 and not as peak load shaving.
The code sections those sources name, each with the edition and the page the book prints it on:
Swipe the table sideways to see the rest of its columns. →
| Code and edition | Section | Printed page |
|---|---|---|
| NEC 2023 | 220.87 | 70-100 |
| NEC 2023 | 220.70 | 70-98 |
| NEC 2023 | 625.42 | 70-557 |
| NEC 2023 | 750.30 | 70-668 |
| NEC 2023 | 210.20(A) | 70-84 |
| NEC 2023 | 625.41 | 70-557 |
| NEC 2023 | Table 310.16 | 70-187 |
| NEC 2023 | 110.14(C)(1)(a)(3) | 70-65 |
| NEC 2023 | 334.80 | 70-226 |
| NEC 2023 | 240.4(D) | 70-123 |
| NEC 2023 | 240.6(A) | 70-124 |
| NEC 2023 | Table 250.122 | 70-158 |
| NEC 2023 | 750.30(C)(1) | 70-669 |
| NEC 2023 | 750.50 | 70-669 |
| NEC 2023 | 220.60 | 70-96 |
| NEC 2023 | 230.90 | 70-114 |
| NEC 2023 | 240.4 | 70-122 |
| NEC 2023 | 110.3(B) | 70-63 |
| NEC 2023 | 750.6 | 70-668 |
| NEC 2023 | 230.42(A)(1) | 70-110 |
| NEC 2023 | 230.79 | 70-113 |
| NEC 2023 | 625.42(B) | 70-557 |
| NEC 2023 | 750.30(C) | 70-668 |
| NEC 2023 | 700.4(C)(1) | 70-626 |
These are NEC 2023 demand rules and referenced tables, looked up and applied by the engine to the service and metered demand you enter, not field measurements. The service headroom is only as good as your metered peak. Any EVEMS must be listed and installed per its instructions; your AHJ and your actual metered demand have final say, and the branch is always sized to the full charger output.
The full receipt, with every source and how each is cross-checked, is on the interactive Biggest EV Charger Calculator.
Ask your assistant
The one rule that makes it reliable: name Intry in your question. That is what tells Claude to run the max_ev_charger tool and answer with the real number, the verdict, and the citation. Leave Intry out and Claude may just guess from memory, which is exactly what you are trying to avoid. Type something like:
What it refuses or sets aside
When you enter a restricted-access adjusted charger rating, it accepts the value but does not apply it, because each condition NEC 625.42(B) attaches is a site fact it cannot check.
Inputs
Swipe the table sideways to see the rest of its columns. →
| Field | Required | Accepts | Range | What it is |
|---|---|---|---|---|
| serviceAmps | yes | number | more than 0 | Service / main breaker rating, e.g. 100, 125, 150, 200. |
| voltage | optional | number | 120 to 240 | Service/charger voltage (default 240; use 120 for Level 1). This tool answers for 120 to 240 V single-phase supply, the same range ev_charger answers for; outside it the call is refused. |
| demandSource | optional | utility, recording | Source of the peak-demand figure (default utility). | |
| demandValue | yes | number | more than 0 | Existing measured peak demand. |
| demandUnit | optional | kw, a | Unit of demandValue (default a). | |
| material | optional | cu, al | Branch conductor material (default cu). | |
| distance | optional | number | 0 or more | One-way run length in feet (informational; default 0). |
| device | optional | shed, throttle, circuit-share | Load-management device TYPE. Omit for the plain 220.87 inverse solve. | |
| deviceRatingAmps | optional | number | more than 0 | shed: the EVSE pass-through breaker; circuit-share: the existing shared-branch breaker; throttle: the EVSE hardware output. |
| hardwareOutputAmps | optional | number | more than 0 | The full EVSE hardware output the branch is protected to. Defaults from device+deviceRatingAmps if omitted. |
| evseAdjustedRatingAmps | optional | number | more than 0 | NEC 625.42(B): the EVSE's OWN restricted-access adjustable rating, if one is set. It is accepted but never applied to the branch: passing it does not shrink the conductor. It returns a blocker naming 625.42(B) / 750.30(C) and the site conditions that would have to be verified first. |
Add Intry to Claude
One paste and Claude can run this tool and the other calculators on Intry's MCP server, right from your phone.
- Claude opens with the Intry connector already filled in. Review it and click Add.
- (If a field is blank, paste the link below into the URL field.)
- In any chat, tap + then Connectors and switch Intry on. Then name Intry in your question (“use Intry to…”) so Claude runs the tool instead of guessing.
https://www.intrysys.com/api/mcpNo login, no API key, and it works on every Claude plan, right from your phone.
Using ChatGPT, Cursor, or a dev tool? See the developer setup on the main page. The endpoint is https://www.intrysys.com/api/mcp.
Every answer comes with the cited NEC section, so you can check it or show an inspector. The numbers come from the same calculator we run on intrysys.com, and our automated checks hold its answers against their sources before anything goes live, for the cases the checks cover, not for every input you can enter.