NEC Article 630 (Electric Welders)
What Size Wire for a Welder?
A welder has its own NEC article, because its duty cycle changes the sizing. Here is the simple home answer, the code duty-cycle method, and the calculator.
The Simple Answer and the Code Answer
The simple answer covers almost every hobby and light-industrial machine: a 50A / 240V circuit, #6 copper, NEMA 6-50. It is robust because a welder is intermittent, so its real heating load is well under a continuous 50A. The code answer lets you size tighter. A welder's duty cycle is how much of a 10-minute period it can weld at full output, and NEC 630.11 multiplies the nameplate rated primary current by a factor from Table 630.11(A) to get the conductor's required ampacity. Then NEC 630.12 sizes the overcurrent device up to 200% of the primary current, using the next lower standard size, which is why a welder breaker can look oversized next to its wire.
NEC Table 630.11(A) Duty-Cycle Factors
| Duty Cycle | 630.11(A) Factor | Conductor Ampacity | Copper Wire |
|---|---|---|---|
| 100% | 1.00 | 50 A | #6 |
| 80% | 0.89 | 44.5 A | #6 |
| 60% | 0.78 | 39 A | #8 |
| 50% | 0.71 | 35.5 A | #8 |
| 40% | 0.63 | 31.5 A | #8 |
| 30% | 0.55 | 27.5 A | #10 |
| 20% or less | 0.45 | 22.5 A | #10 |
Wire is the 60°C copper needed for the duty-cycle ampacity of a 50A-primary welder; scale the same way for your welder's rated primary current. The breaker is separate: up to 200% of the primary current (NEC 630.12), so a 50A-primary welder may use up to a 100A breaker, though a receptacle-fed install is sized to the receptacle instead.
Size Your Welder Circuit
Enter the duty-cycle conductor ampacity (rated primary current x the factor above) as the load to get the wire, then add your run to check voltage drop.
Frequently Asked Questions
What size wire and breaker for a welder?
For a typical 240V home welder, the simple robust answer is a 50A circuit with #6 copper on a NEMA 6-50 receptacle, which handles essentially any hobby stick, MIG, or small multiprocess machine. If you want the code minimum, NEC 630.11 sizes the conductor from the welder's rated primary current times a duty-cycle factor (Table 630.11(A)): a welder that only runs part of the time draws a smaller effective load, so the wire can be smaller. NEC 630.12 then allows the breaker to be as large as 200% of the rated primary current, so the breaker is often bigger than the wire's normal rating, on purpose.
What is the welder duty-cycle wire rule (NEC 630.11)?
A welder's duty cycle is the fraction of a 10-minute period it can weld at full output; a 60% duty cycle means 6 minutes welding, 4 minutes cooling. Because it is not welding continuously, NEC 630.11 lets you multiply the nameplate rated primary current by a factor from Table 630.11(A) to get the conductor's required ampacity: 100% duty = 1.00, 80% = 0.89, 60% = 0.78, 50% = 0.71, 40% = 0.63, 30% = 0.55, 20% or less = 0.45. Example: a 50A-primary welder at 60% duty needs a conductor rated for 50 x 0.78 = 39A, which is #8 copper.
Why can the welder breaker be bigger than the wire?
Because NEC 630.12 sizes the overcurrent device for the welder, not just the conductor. It permits an overcurrent device up to 200% of the rated primary current (using the next lower standard size if 200% is not a standard rating). The duty-cycle-sized conductor from 630.11 is protected for the intermittent welding load, and the larger breaker keeps it from nuisance-tripping on the heavy momentary draw when an arc strikes. This is similar to a motor circuit, where the wire and the breaker are sized by different rules.
Can I run a welder on a 50 amp circuit?
Yes, that is the most common home setup. A 50A / 240V circuit with #6 copper on a NEMA 6-50 receptacle covers the great majority of 240V hobby and light-industrial welders, because their rated primary current at usable duty cycles falls at or below what a 50A circuit supplies. Check the welder's nameplate rated primary amps; if it is 40A or below, a 50A circuit is comfortable. Larger machines that call out a higher primary current need a circuit sized to their nameplate.
What plug does a welder use?
The most common 240V welder plug is the NEMA 6-50 (50A), the same style used for many stick and MIG welders, paired with a 50A circuit and #6 copper. Smaller 240V welders may use a NEMA 6-30 (30A, #10 copper) or 6-20 (20A, #12). Match the receptacle, breaker, and wire to each other and to the welder's rated primary current; the machine's cord cap tells you which receptacle the manufacturer expects.
Related
Air Compressor Wire Size
Another shop motor load with a small-wire, big-breaker character.
Wire Size for Appliances
Dryer, range, water heater, AC, and more: the circuit for each.
Wire Size Calculator
Size any load per NEC 310.16 with derating and voltage drop.
Voltage Drop Calculator
Check the drop on a long run out to the shop or garage.