NEC Article 630 (Electric Welders)

What Size Wire for a Welder?

A welder has its own NEC article, because its duty cycle changes the sizing. Here is the simple home answer, the code duty-cycle method, and the calculator.

Quick answer: For a 240V home welder whose nameplate allows it, run a 50A circuit with #6 copper to a NEMA 6-50 receptacle. The code minimum can be smaller: NEC 630.11 sizes the conductor at the rated primary current times a duty-cycle factor, and NEC 630.12 lets the breaker go up to 200% of the primary current, so the breaker can be larger than the wire on purpose.

The Simple Answer and the Code Answer

The simple answer, where the nameplate allows it: a 50A / 240V circuit, #6 copper, NEMA 6-50. It is robust because a welder is intermittent, so its real heating load is well under a continuous 50A. The code answer lets you size tighter. A welder's duty cycle is how much of a 10-minute period it can weld at full output, and NEC 630.11 multiplies the nameplate rated primary current by a factor from Table 630.11(A) to get the conductor's required ampacity. Then NEC 630.12 sizes the overcurrent device up to 200% of the primary current, using the next lower standard size, which is why a welder breaker can look oversized next to its wire.


NEC Table 630.11(A) Duty-Cycle Factors

Conductor ampacity example for a 50A rated-primary arc welder, copper. Ampacity = primary current x factor (NEC 630.11).

Swipe the table sideways to see the rest of its columns. →

Duty Cycle630.11(A) FactorConductor AmpacityCopper Wire
100%1.0050 A#6
80%0.8944.5 A#6
60%0.7839 A#8
50%0.7135.5 A#8
40%0.6331.5 A#8
30%0.5527.5 A#10
20% or less0.4522.5 A#10

Wire is the 60°C copper needed for the duty-cycle ampacity of a 50A-primary welder; scale the same way for your welder's rated primary current. The breaker is separate: up to 200% of the primary current (NEC 630.12), so a 50A-primary welder may use up to a 100A breaker, though a receptacle-fed install is sized to the receptacle instead.


Size Your Welder Circuit

It opens on the 50 A welder circuit above. For your welder, enter the duty-cycle conductor ampacity (rated primary current x the factor above) as the load and leave Continuous load off to get the wire; the breaker line is a general-circuit value, not the NEC 630.12 welder breaker. For a long run, the result links to the voltage drop calculator, which checks that wire over your run; this tool does not size for voltage drop.

Loading calculator...

The code sections this page cites are named in the source receipt.


Frequently Asked Questions

What size wire and breaker for a welder?

For a 240V home welder whose nameplate allows it, the simple robust answer is a 50A circuit with #6 copper on a NEMA 6-50 receptacle. If you want the code minimum, NEC 630.11 sizes the conductor from the welder's rated primary current times a duty-cycle factor (Table 630.11(A)): a welder that only runs part of the time draws a smaller effective load, so the wire can be smaller. NEC 630.12 then allows the breaker to be as large as 200% of the rated primary current, so the breaker can be bigger than the wire's normal rating, on purpose.

What is the welder duty-cycle wire rule (NEC 630.11)?

A welder's duty cycle is the fraction of a 10-minute period it can weld at full output; a 60% duty cycle means 6 minutes welding, 4 minutes cooling. Because it is not welding continuously, NEC 630.11 lets you multiply the nameplate rated primary current by a factor from Table 630.11(A) to get the conductor's required ampacity: 100% duty = 1.00, 80% = 0.89, 60% = 0.78, 50% = 0.71, 40% = 0.63, 30% = 0.55, 20% or less = 0.45. Example: a 50A-primary welder at 60% duty needs a conductor rated for 50 x 0.78 = 39A, which is #8 copper.

Why can the welder breaker be bigger than the wire?

Because NEC 630.12 sizes the overcurrent device for the welder, not just the conductor. It permits an overcurrent device up to 200% of the rated primary current (using the next lower standard size if 200% is not a standard rating). The duty-cycle-sized conductor from 630.11 is protected for the intermittent welding load, and the larger breaker keeps it from nuisance-tripping on the heavy momentary draw when an arc strikes. This is similar to a motor circuit, where the wire and the breaker are sized by different rules.

Can I run a welder on a 50 amp circuit?

Yes, where the welder's nameplate allows it. A 50A / 240V circuit with #6 copper on a NEMA 6-50 receptacle covers a welder whose rated primary current at its duty cycle falls at or below what a 50A circuit supplies. Check the welder's nameplate rated primary amps; if it is 40A or below, a 50A circuit is comfortable. Larger machines that call out a higher primary current need a circuit sized to their nameplate.

Does a welder circuit need GFCI protection?

GFCI: plugged into a receptacle in a dwelling location NEC 2023 210.8(A) lists (210.8(A)(2) "Garages and also accessory buildings that have a floor located at or below grade level not intended as habitable rooms and limited to storage areas, work areas, and areas of similar use"), a welder needs GFCI protection; 210.8(A) reaches 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground. Hardwired, it has no receptacle for 210.8(A) to reach, and 2023 210.8(D)'s list does not name it. Which edition applies is the one your jurisdiction has adopted.

What plug does a welder use?

A 240V welder plug can be the NEMA 6-50 (50A), used on stick and MIG welders, paired with a 50A circuit and #6 copper. Smaller 240V welders may use a NEMA 6-30 (30A, #10 copper) or 6-20 (20A, #12). Match the receptacle, breaker, and wire to each other and to the welder's rated primary current; the machine's cord cap tells you which receptacle the manufacturer expects.


Related