NEC Article 625 EV Charging

NEMA 6-50 Wire Size for EV Charging

A NEMA 6-50 is a 50-amp, 240-volt receptacle with no neutral, the clean and cheap outlet for a plug-in EV charger or a welder. Here is the wire, breaker, ground, and GFCI it needs.

Quick answer: A NEMA 6-50 needs #6 copper (or #4 aluminum) on a 50A GFCI breaker, with a #10 copper ground and no neutral (6/2 cable, two hots and a ground). Aluminum on a receptacle: the receptacle's terminals must be identified for aluminum conductors (NEC 2023, 110.14(A)). #8 copper holds only on 75°C-marked terminations (NEC 110.14(C)(1)(a)); #6 holds on any and is required for NM-B. A plug-in charger on a 6-50 is capped at 40A continuous (9.6 kW), same as a 14-50.

NEMA 6-50 Circuit Spec

NEMA 6-50 receptacle circuit for a Level 2 EV charger, NEC Article 625

Swipe the table sideways to see the rest of its columns. →

Receptacle / circuit rating50A, 240V
Configuration2 hots + ground (no neutral)
Cable6/2 (vs 6/3 for a 14-50)
Breaker (double-pole, GFCI)50A
Copper wire (standard)#6
Copper wire (75°C-marked terminations only)#8
Aluminum wire (receptacle terminals identified for aluminum, NEC 2023, 110.14(A))#4
Equipment ground (Cu)#10
Max continuous charge (plug-in)40A (9.6 kW)

Same conductors as a 14-50 minus the neutral: #6 copper covers the 50A circuit at both the 60°C and 75°C columns of NEC Table 310.16. Ground per NEC 250.122. GFCI per NEC 625.54. Check voltage drop on runs over about 100 feet.


Why a 6-50 Has No Neutral

A charger that draws only across the two hot legs uses the ground for safety and no neutral (some chargers do require one: Eaton's EV wall charger manual prints “Neutral required”, so check yours). For a charger with no neutral, a NEMA 6-50 gives it exactly that, two hots and a ground, so you pull 6/2 cable instead of the 6/3 a 14-50 needs. That saves a conductor and some cost and is perfectly code-compliant for EV charging. The only reason to choose a 14-50 instead is versatility: an RV, a range, or another appliance that needs 120V from the neutral. For an EV-only or welder outlet, the 6-50 is the cleaner install.

The documents behind these figures, and the code sections this page cites, are named in the source receipt.


Your Exact Run: Wire, Panel, and Parts

The calculator opens on a 50A receptacle at 40A continuous. It models the receptacle as a 14-50, so leave the neutral and the 14-50R out of the parts list for a 6-50; the GFCI breaker (NEC 625.54) and the wire are the same. The wire it shows is the 75°C THHN minimum; 6/3 or 6/2 NM-B cable needs #6 copper, the size quoted above. Enter your run length and panel to get the exact wire, voltage drop, panel-capacity check, GFCI note, and a parts list.

Loading calculator...

Frequently Asked Questions

What size wire for a NEMA 6-50 outlet?

Use #6 copper (or #4 aluminum) on a 50A double-pole breaker with a #10 copper equipment ground (#8 if the ground is aluminum), because a NEMA 6-50 is a 50A / 240V receptacle. Aluminum on a receptacle: the receptacle's terminals must be identified for aluminum conductors (NEC 2023, 110.14(A)). The difference from a 14-50 is that a 6-50 has no neutral, so it uses 6/2 cable (two hots and a ground) instead of 6/3. #8 copper carries a 50A circuit only on 75°C-marked terminations (NEC 110.14(C)(1)(a)), so #6 is the answer that holds on any termination and is required if the run is NM-B cable, which uses the 60°C column where #8 is only rated 40A.

What is the difference between a NEMA 6-50 and a 14-50?

The neutral. A NEMA 14-50 has two hots, a neutral, and a ground (4 wires, 6/3 cable); a NEMA 6-50 has two hots and a ground only (3 wires, 6/2 cable). A charger that draws only across the two hots never uses the neutral, so a 6-50 gives it everything it needs while saving a conductor; some chargers require a neutral (Eaton's EV wall charger manual prints "Neutral required"), so check the charger's instructions first. Both are 50A / 240V and both cap a plug-in charger at 40A continuous. A 14-50 is more versatile for non-EV uses (RVs, welders, ranges that need 120V accessories); a 6-50 is the cleaner, cheaper choice when the outlet is only for EV charging or a welder.

How many amps can an EV charger on a NEMA 6-50 draw?

40 amps continuous, the same as a 14-50. A plug-in EVSE on a 50A receptacle is limited to 80% of the circuit for a continuous load (NEC 210.20(A), 625.42), so a 6-50 tops out at 40A / 9.6 kW. To charge at 48A you need a hardwired charger on a 60A circuit, not any 50A plug.

Does a NEMA 6-50 for an EV charger need a GFCI breaker?

Yes. NEC 625.54 requires GFCI protection for a cord-and-plug (receptacle-connected) EV charger, so a NEMA 6-50 feeding an EVSE must be on a 50A two-pole GFCI breaker. NEC 625.54 covers receptacles, and a hardwired charger has none. At a dwelling, the 2023 NEC's 210.8(F) requires GFCI protection for an outdoor outlet and for an outlet in a garage with its floor at or below grade, an accessory building or a boathouse, on a single-phase circuit of 150 V or less to ground and 50 A or less; a hardwired charger's outlet there needs it.

Can I use a NEMA 6-50 for a welder and an EV charger?

The outlet is electrically the same 50A / 240V circuit either device would use, and the 6-50 is a common welder receptacle. But you cannot plug both in and run them at once on one circuit, and a permanently installed EV charger must be on its own individual branch circuit (NEC 625.40). A shared 6-50 works for occasional, one-at-a-time use of a plug-in welder or a plug-in EV mobile connector, not for a hardwired charger.


Related EV References