NEC Article 625 EV Charging

NEMA 14-50 Wire Size for EV Charging

A NEMA 14-50 is a 50-amp, 240-volt receptacle, a plug for a Level 2 EV charger. Here is the wire, breaker, ground, and GFCI it needs, plus the 40-amp continuous limit that catches people out.

Quick answer: A NEMA 14-50 needs #6 copper (or #4 aluminum) on a 50A breaker, with a #10 copper ground and a GFCI breaker (NEC 625.54). Aluminum on a receptacle: the receptacle's terminals must be identified for aluminum conductors (NEC 2023, 110.14(A)). #8 copper holds only on 75°C-marked terminations (NEC 110.14(C)(1)(a)), and #6 is standard and is required for NM-B cable. A plug-in charger on a 14-50 is capped at 40A continuous (9.6 kW).

NEMA 14-50 Circuit Spec

NEMA 14-50 receptacle circuit for a Level 2 EV charger, NEC Article 625

Swipe the table sideways to see the rest of its columns. →

Receptacle / circuit rating50A, 240V
Breaker (double-pole, GFCI)50A
Copper wire (standard)#6
Copper wire (75°C-marked terminations only)#8
Aluminum wire (receptacle terminals identified for aluminum, NEC 2023, 110.14(A))#4
Equipment ground (Cu)#10
Max continuous charge (plug-in)40A (9.6 kW)

#6 copper covers the 50A circuit at both the 60°C and 75°C columns of NEC Table 310.16 and is the standard choice; #8 copper is the 75°C-only minimum, and it holds only where the breaker and the receptacle are both listed and identified for 75°C conductors (NEC 110.14(C)(1)(a)(3)). Ground per NEC 250.122. GFCI per NEC 625.54. Check voltage drop on runs over about 100 feet.


Why a 14-50 Charges at 40A, Not 50A

EV charging is a continuous load (three hours or more), and NEC 625.41 requires the branch breaker to be at least 125% of the charger's load. On a 50A circuit that is 40A, so any plug-in charger on a NEMA 14-50 is set to draw 40A maximum, about 9.6 kW. This is why a 48A charger cannot run on a 14-50: 48A needs a 60A circuit, which means a hardwired connection, not a plug. If you want the full 48A / 11.5 kW, hardwire the charger.


Your Exact Run: Wire, Panel, and Parts

The calculator opens on a NEMA 14-50 outlet at 40A. The wire it shows is the 75°C THHN minimum; 6/3 NM-B cable needs #6 copper, the size quoted above. Enter your run length and panel to get the exact wire, voltage drop, panel-capacity check, GFCI note, and a parts list.

Loading calculator...

Frequently Asked Questions

What size wire for a NEMA 14-50 outlet?

Use #6 copper (or #4 aluminum) on a 50A double-pole breaker, with a #10 copper equipment ground (#8 if the ground is aluminum), because a NEMA 14-50 is a 50A / 240V receptacle. Aluminum on a receptacle: the receptacle's terminals must be identified for aluminum conductors (NEC 2023, 110.14(A)). #8 copper carries 50A only at the 75°C column of NEC Table 310.16, which on a 50A circuit holds only where the breaker and the receptacle are both listed and identified for 75°C conductors (NEC 110.14(C)(1)(a)(3)); on 60°C terminations or NM-B cable (NEC 334.80) #8 carries only 40A, so #6 is the answer that holds on any termination, and it also keeps voltage drop low. A 14-50 is a 4-wire device (two hots, a neutral, and a ground); a charger that draws only across the two hots leaves the neutral unused, but the receptacle still has the terminal, and some chargers require it (Eaton's EV wall charger manual prints "Neutral required").

Can I use #8 wire for a NEMA 14-50?

Only on 75°C-rated terminals with conductors like THHN/THWN-2 in conduit, where #8 copper carries 50A and technically satisfies the 50A circuit. #6 holds on either terminal rating, and #8 is not allowed if the run is NM-B (Romex), because NM-B uses the 60°C column where #8 copper is only rated 40A, below the 50A circuit. When in doubt, use #6 copper.

How many amps can an EV charger on a NEMA 14-50 draw?

40 amps continuous. EV charging is a continuous load, and NEC 625.41 sizes the 50A breaker at not less than 125% of the charger's load (50 ÷ 1.25 = 40A), so a NEMA 14-50 tops out at 40A / 9.6 kW no matter what the car could accept. To charge at 48A you need a hardwired charger on a dedicated 60A circuit, not a 14-50 plug.

Does a NEMA 14-50 for an EV charger need a GFCI breaker?

Yes. NEC 625.54 requires GFCI protection for a cord-and-plug (receptacle-connected) EV charger, so a NEMA 14-50 feeding an EVSE must be on a GFCI breaker. Use a 50A two-pole GFCI breaker listed for the panel. NEC 625.54 covers receptacles, and a hardwired charger has none. At a dwelling, the 2023 NEC's 210.8(F) requires GFCI protection for an outdoor outlet and for an outlet in a garage with its floor at or below grade, an accessory building or a boathouse, on a single-phase circuit of 150 V or less to ground and 50 A or less; a hardwired charger's outlet there needs it.

Does a NEMA 14-50 need a dedicated circuit?

Yes, for EV charging. The receptacle must be the only outlet on its branch circuit (an individual branch circuit) so the full 50A is available to the charger, per NEC 625.40. Sharing the circuit with other outlets is not permitted for an EVSE install.

The documents behind these figures, and the code sections this page cites, are named in the source receipt.


Related EV References