Conductor Reference

THHN vs THWN Wire

What the letters mean, why a dual-rated spool is both at once, and the one termination rule that decides how much of the rating you actually get to use.

Quick answer: THHN is rated 90°C for dry locations; THWN is rated 75°C and approved for wet locations. Wire printed THHN/THWN-2 is dual-rated, the same conductor rated 90°C wet or dry, so on that wire the “versus” is moot. Same copper, same nylon jacket, same conduit fill. The catch: per NEC 110.14(C), your terminals' rating caps the ampacity, so the 90°C rating is derating headroom, not a bigger breaker.

Ampacity from NEC Table 310.16; insulation types per NEC Table 310.4(1); termination limits per NEC 110.14(C). NFPA 70 2023. Confirm the marking on your specific conductor.

THHN vs THWN, Side by Side

THHN vs THWN building wire. Ampacity from NEC Table 310.16 (90°C column for THHN, 75°C for THWN); insulation ratings per NEC Table 310.4(1); termination limits per NEC 110.14(C). NFPA 70 2023. Dimensions derived from the same verified conductor-area table.

Swipe the table sideways to see the rest of its columns. →

AttributeTHHNTHWN
NameThermoplastic High Heat-resistant Nylon-coatedThermoplastic Heat- and Water-resistant Nylon-coated
Temperature rating90°C (194°F)75°C (167°F)
Approved locationsDry and damp onlyWet, damp, and dry
NEC 310.16 ampacity column90°C column75°C column
#12 copper ampacity (its column)30 A25 A
#10 copper ampacity (its column)40 A35 A
Conductor + nylon jacket dimensionsIdenticalIdentical (same conductor)
Cross-sectional area, #12 (fill)0.0133 in²0.0133 in²
Wet raceway, outdoors, undergroundNot rated on its ownRated (wet location)
What is actually on the spoolDual-rated THHN/THWN-2Dual-rated THHN/THWN-2

The Part That Is Easy to Get Wrong: 90°C Is Not Your Ampacity

  • Terminals set the ceiling. NEC 110.14(C) ties the circuit ampacity to the lowest-rated termination in the path: 60°C at 100 amperes or less and 75°C above it, each unless the equipment is listed and marked otherwise, so you size the conductor from that column, not the 90°C column, even with THHN.
  • The 90°C column is for derating. Its real job is to give you a higher starting ampacity before temperature correction and conductor-bundling adjustments. You apply those factors to the 90°C number, then compare the result to the terminal rating and take the smaller. That is where THHN earns its keep, in hot attics and crowded raceways.
  • #12 copper is still a 20 A conductor. THHN #12 shows 30 A in the 90°C column, but on a 75°C terminal it is a 25 A conductor, and the 20 A breaker on it comes from the small-conductor rule in 240.4(D). The 90°C rating never turns a #12 into a 30 A branch circuit.

Frequently Asked Questions

Are THHN and THWN the same wire?

Where the jacket prints both, yes, physically. Dual-rated THHN/THWN-2 carries both markings on the same conductor: a stranded or solid copper (or aluminum) conductor with PVC insulation and a nylon jacket, dimensionally identical either way. THHN is the dry-location, 90°C rating and THWN (specifically THWN-2) is the wet-location, 90°C rating. So a reel printed with both is both at once, and it takes the higher of the two ratings for the location you are in.

What is the difference between THHN and THWN?

The letters spell it out. THHN is Thermoplastic High Heat-resistant Nylon-coated, rated 90°C but for dry and damp locations only. THWN is Thermoplastic Heat- and Water-resistant Nylon-coated, rated 75°C and approved for wet locations. THWN-2 is the water-resistant type bumped to 90°C in both wet and dry. In NEC Table 310.16 you read THHN in the 90°C column and plain THWN in the 75°C column, which is why the same #12 copper is 30 A as THHN and 25 A as THWN in their respective columns.

Can I use the 90°C THHN ampacity for my circuit?

Not as the final answer where the terminals are rated lower, and this is the mistake that trips people up. Per NEC 110.14(C), the ampacity is limited by the temperature rating of the terminals, and the section sets that column from the circuit rating: 60°C at 100 amperes or less, 75°C above it, each one unless the equipment is listed and marked otherwise. You use the 90°C column only as the starting point for temperature-correction and conductor-bundling adjustments, then the terminal rating governs the final ampacity. So THHN's higher number is derating headroom for hot or crowded conduit, not a license to load the conductor to 90°C.

Can THHN be used in wet locations or underground?

Not on its THHN rating alone. In a wet location, in underground conduit, or anywhere water can enter the raceway, you need the wet-location rating, which is THWN or THWN-2. Because modern wire is dual-rated THHN/THWN-2, the exact same reel is fine wet, but you are relying on the THWN-2 marking to make it legal, not the THHN marking. If a conductor is marked THHN only, keep it dry.


Related Tools

Same wire, different rating. Size it right.

Read THHN at 90°C for derating, then let the terminal rating cap the ampacity. The wire size calculator does both from NEC Table 310.16.