Code Reference

NEC 2023 vs 2026 Dwelling Load Calculation

The main changes in a residential load calculation from the 2023 to the 2026 National Electrical Code, read from both books side by side, with a same-house worked example run under both editions.

Quick answer: The 2026 NEC moves load calculations from Article 220 to Article 120, cuts the dwelling general lighting load from 3 VA to 2 VA per square foot for service and feeder sizing, drops the optional method’s 100 percent first tier from 10 kVA to 8 kVA, and counts EV chargers at 100 percent of their 120.57 load under new 120.82(D), with the 7,200 VA minimum gone. For the same house counted the same way (living area only, the charger at 100 percent in both), the 2026 optional-method calculation comes out lower (about 6 percent on the worked example below), because both the smaller first tier and the lighting cut reduce the calculated demand; adding load to an existing house can come out higher (120.83, below).

Load-calculation changes only, read from NFPA 70, 2023 edition, and NFPA 70, 2026 edition, each row by section; the printed pages are in the code index below. Your adopted edition and AHJ govern.

What Changed, Side by Side

Dwelling load-calculation changes from the 2023 to the 2026 National Electrical Code, each row read from NFPA 70, 2023 edition, and NFPA 70, 2026 edition, at the section shown. The 2 VA/ft² figure is for service and feeder sizing; the 3 VA/ft² basis is kept for counting required branch circuits (120.13). Your adopted edition and AHJ govern.

Swipe the table sideways to see the rest of its columns. →

Load-calculation ruleNEC 2023NEC 20262026 section
Load-calculation articleArticle 220Article 120, same titleArt. 220 to 120
Dwelling general lighting + receptacle load (service and feeder sizing)3 VA/ft22 VA/ft2120.41 (was 220.41)
Floor area for the lighting loadOptional method: leaves out open porches, garages, and unused or unfinished spaces not adaptable for future use (other methods: open porches and unfinished areas)Standard, optional and existing-dwelling methods: leave out detached garages, open porches, and unfinished areas not adaptable for future use120.5(C) (was 220.5(C) and 220.82(B))
General lighting basis for counting required branch circuits3 VA/ft23 VA/ft2 (unchanged)120.13 (2023: 220.41)
Optional method: general loads taken at 100%First 10 kVAFirst 8 kVA120.82(B) (was 220.82(B))
Optional method: remainder demand factor40%40% (unchanged)120.82(B) (was 220.82(B))
EVSE loadThe larger of 7,200 VA or the nameplateThe nameplate, or 7,200 VA if none is available120.57 (was 220.57)
EVSE in the optional methodNot named in the optional methodAt 100% of its 120.57 load, outside the tier120.82(D) (new)
Continuous loads inside the load calculationNo general rule in Article 220Not required at 125%120.5(E) (new)
Existing dwelling: load added to a houseFirst 8 kVA at 100%, the rest at 40%; added air conditioning or central electric heat at 100%First 8 kVA of existing and new load at 100%, the rest of the existing load at 40%; beyond that, new EVSE and new central electric resistance heat at 80%, other new loads at 50%120.83 (was 220.83)
Existing loads from metered demandMaximum demand at 125% plus the new loadThe same, minus any removed load120.87 (was 220.87)

Same House, Both Editions: A Worked Example

A 2,400 square foot dwelling (living area, no garage) with an electric range, water heater, dryer, dishwasher, disposal, and microwave, plus central AC and a 40 A Level 2 EV charger, run through the optional method (NEC 220.82 in 2023, 120.82 in 2026). The AC and the EV charger are added at 100 percent in both columns, so the only things moving the answer are the two edition changes: the lighting cut and the smaller first tier. The 2023 column is our load calculator’s own answer for this house.

Optional-method dwelling load calculation, same house under NEC 2023 and NEC 2026. Appliance values are illustrative nameplates. The EV charger is added at 100 percent in both columns: the 2026 edition requires it (120.82(D)); the 2023 optional method names no EVSE, and adding it at 100 percent is our load calculator’s conservative choice.

Swipe the table sideways to see the rest of its columns. →

LoadNEC 2023NEC 2026
General lighting + receptacles (2,400 ft²)3 VA/ft² = 7,200 VA2 VA/ft² = 4,800 VA
Small-appliance branch circuits (2)3,000 VA3,000 VA
Laundry branch circuit1,500 VA1,500 VA
Fastened-in-place appliances (nameplate)25,100 VA25,100 VA
General connected load36,800 VA34,400 VA
General demand (first tier at 100% + 40% of remainder)10,000 + 40% = 20,720 VA8,000 + 40% = 18,560 VA
Central AC (100%, the largest of the heating and cooling selections)6,000 VA6,000 VA
EV charger, 40 A (100% of its nameplate)9,600 VA9,600 VA
Total calculated load36,320 VA34,160 VA
Minimum service (total ÷ 240 V)151.3 A142.3 A
Next size in the load calculator's list of dwelling services200 A150 A
Smallest Table 240.6(A) rating at or above it175 A150 A
The punchline: the same house calculates to 151.3 A under the 2023 code, more than a 150 A service carries, but only 142.3 A under the 2026 code, which a 150 A service carries. Both 2026 changes push the number down, the smaller first tier by 1,200 VA and the lighting cut by 960 VA, and together they bring this house under the 150 A line. Under 2023 the load calculator’s list goes to 200 A; the smallest Table 240.6(A) rating at or above 151.3 A is 175 A.

Does the 2026 Code Shrink or Grow Your Service?

  • In the optional method, both changes make it smaller. The 2026 edition lowers the calculated load two ways at once. On the worked house they add up to about 6 percent less than the 2023 result, which is enough to change the service size on a house near a breakpoint.
  • The smaller first tier. Dropping the 100 percent tier from 10 kVA to 8 kVA moves 2 kVA from the 100 percent band into the 40 percent band, which cuts the calculated demand by 1,200 VA once the general loads pass 10 kVA. On such a house under about 3,000 square feet this is the larger of the two reductions.
  • The lighting cut adds to it. The 3 VA to 2 VA per square foot reduction takes 1 VA off every square foot; on a 2,400 square foot house that is 960 VA of demand after the 40 percent factor. Because it scales with floor area, it overtakes the tier change above about 3,000 square feet.
  • Three things can push the other way. New 120.82(D) puts an EV charger in at 100 percent of its 120.57 load; if a 2023 calc put the charger in the 40 percent remainder, which the 2023 optional method does not settle, the 2026 number can land higher. The 2026 optional method counts an attached garage in the floor area (120.5(C)), where the 2023 one left garages out. And the existing-dwelling method (120.83) takes a new EV charger at 80 percent and other new loads at 50 percent past the first 8 kVA, where 2023’s first table took them in its 40 percent remainder, so adding such load to a house can calculate higher (added air conditioning and central electric heat went in at 100 percent in 2023, so for those 2026 is lower). When we add the charger at 100 percent in both editions and count living area only, as here, the 2026 optional-method result stays lower.
  • The 7,200 VA EVSE minimum is gone. Under 2023 a charger counts at least 7,200 VA; under 2026 it counts its nameplate, and 7,200 VA only where there is no nameplate (120.57). A small Level 2 charger counts less in 2026.
  • The 125 percent factor, in words. 120.5(E) says load calculations shall not require continuous loads to be calculated at 125 percent. The 125 percent still applies where conductors and overcurrent devices are sized, so the final wire and breaker do not shrink; the math lives in a different place.

Which Edition Do You Run?

Publication is not adoption. Nothing here applies until your jurisdiction adopts the 2026 edition. Massachusetts (since April 24, 2026), Maine (since July 1, 2026), North Dakota (since July 1, 2026), Colorado (since August 1, 2026), Minnesota (since August 17, 2026), Texas (since September 1, 2026), Arkansas (since September 3, 2026) and Oregon (since October 1, 2026) are on the 2026 NEC, and 31 of the 51 jurisdictions we track name the 2023 or 2020 edition in a state rule or code (some reach only some buildings). Run your load calc under the code your AHJ enforces, and confirm the edition before you bid or pull the permit: NEC adoption by state table.

Run this in your AI. Ask Claude or ChatGPT to check whether your existing panel can carry a new load under NEC 220.87 and it runs the Intry Existing-Load Panel Check live, handing back the verdict with its cited source instead of a guess. Then keep the reading as one job in the Intry app.

Frequently Asked Questions

Does the 2026 NEC make a dwelling load calculation bigger or smaller?

By the optional method, smaller for the same house counted the same way. The general lighting and receptacle load drops from 3 VA to 2 VA per square foot, and the optional method's 100 percent first tier shrinks from 10 kVA to 8 kVA, which moves 2 kVA into the 40 percent remainder and cuts the demand by about 1,200 VA once the general loads pass 10 kVA. For such a house, below about 3,000 square feet the tier change is the larger of the two. A charger whose nameplate is under 7,200 VA also counts less, because the 2023 minimum is gone (120.57). On the worked house below the result is about 6 percent under 2023. Three things can push the other way: the 2026 optional method counts an attached garage in the floor area (120.5(C)); new 120.82(D) puts an EV charger at 100 percent, where a 2023 calculation that put it in the 40 percent remainder came out lower; and the existing-dwelling method (120.83) takes a new EV charger at 80 percent and other new loads at 50 percent past the first 8 kVA, where 2023's first table took them in its 40 percent remainder, so adding such load to a house can calculate higher under 2026. (Added air conditioning and central electric heat went in at 100 percent in 2023, so for those 2026 is lower.)

Is the 3 VA per square foot lighting load gone in the 2026 NEC?

No, and this trips people up. The lighting load drops to 2 VA per square foot only for sizing the service and feeder (120.41, and the optional method's 120.82(B)). 120.13 keeps 3 VA per square foot "for calculating minimum branch circuits required". So you size the service with 2 VA and still count branch circuits with 3 VA. In the 2023 edition one figure, 3 VA in 220.41, did both jobs.

Which NEC edition do I actually use for my load calc?

Whichever edition your jurisdiction has adopted, not whichever is newest. Massachusetts (since April 24, 2026), Maine (since July 1, 2026), North Dakota (since July 1, 2026), Colorado (since August 1, 2026), Minnesota (since August 17, 2026), Texas (since September 1, 2026), Arkansas (since September 3, 2026) and Oregon (since October 1, 2026) are on the 2026 NEC, and 31 of the 51 jurisdictions we track name the 2023 or 2020 edition in a state rule or code (some reach only some buildings). Publication is not adoption. Run the numbers under the edition your AHJ enforces, and check the adoption table before you bid or pull a permit.


Related Tools

Know your edition, then run the numbers.

The same house sizes differently under 2023 and 2026. Confirm which code your jurisdiction enforces, then let the calculator show every line.