Conduit Reference

Types of Electrical Conduit

Every common conduit type, the NEC article that governs it, where it is allowed, and a full fill matrix so you can see at a glance how many wires each holds.

Quick answer: Conduit falls into three groups. Rigid metal (EMT, IMC, RMC) for exposed runs and physical protection; rigid PVC for wet, underground, and corrosive locations; and flexible types (ENT, FMC, LFMC, LFNC) for concealed work and equipment connections. Each has its own NEC article. IMC holds the most conductors through 2 inch trade size (EMT takes over at 2-1/2 inch and larger), and Schedule 80 PVC holds the fewest at every size.

Internal areas from NEC Chapter 9 Table 4; fill limit from Table 1; article numbers from NEC Chapter 3. NFPA 70 2023. Confirm your AHJ’s adopted edition and any local amendments.

The Conduit Types, With Their NEC Articles

Swipe the table sideways to see the rest of its columns. →

TypeNameNEC ArticleBest forLocations
EMTElectrical Metallic TubingArt. 358Dry, exposed indoor and commercial runsDry, damp, and wet; in wet locations couplings and connectors comply with 314.15; direct burial with identified fittings and corrosion protection; not where subject to severe physical damage
IMCIntermediate Metal ConduitArt. 342Physical protection, outdoors, hazardous locations; lighter than RMCAll, including wet, underground, and hazardous (with corrosion protection)
RMCRigid Metal ConduitArt. 344Maximum mechanical protection and hazardous locationsAll, including wet, underground, and hazardous (with corrosion protection)
PVCRigid PVC Conduit (Schedule 40 / 80)Art. 352Wet, underground, and corrosive locations; needs a pulled EGCWet, underground, corrosive; Schedule 80 where exposed to physical damage
ENTElectrical Nonmetallic TubingArt. 362Concealed in walls, floors, and ceilings; concrete-encasedConcealed or protected; not for exposed severe-damage or most plenum uses
FMCFlexible Metal ConduitArt. 348Short connections to motors and fixtures where flexibility is neededDry locations; not where liquids are present unless liquidtight
LFMCLiquidtight Flexible Metal ConduitArt. 350Flexible connections in wet or oily areas, outdoor equipment, HVACWet locations; direct burial where listed
LFNCLiquidtight Flexible Nonmetallic ConduitArt. 356Flexible, corrosion-resistant connections in wet locationsWet and corrosive; needs a pulled EGC

Conduit Fill by Type: #12 THHN Matrix

How many #12 THHN conductors each conduit type holds at the NEC 40 percent fill limit, every trade size side by side. The pattern holds for other conductor sizes: IMC is roomiest through 2 inch trade size, EMT takes over as roomiest at 2-1/2 inch and larger, and Schedule 80 PVC is tightest at every size, because the ranking is set by each type’s internal area.

Maximum #12 THHN conductors per conduit type at the NEC 40% fill limit (three or more conductors). Internal areas from NEC Chapter 9 Table 4; fill from Table 1; #12 THHN area 0.0133 sq in from Table 5. NFPA 70 2023. ENT is listed only through 2 inch.

Swipe the table sideways to see the rest of its columns. →

Trade sizeEMTIMCRMCPVC-40PVC-80ENT
1/2"9109868
3/4"161716151215
1"262926252025
1-1/4"454946433743
1-1/2"616762595159
2"101109102998699
2-1/2"176154146141124n/a
3"266238225218193n/a
3-1/2"347318301293261n/a
4"443410387377338n/a

Frequently Asked Questions

What are the main types of electrical conduit?

The common types split into rigid metal, rigid nonmetallic, and flexible. Rigid metal is EMT (thin-wall steel, NEC Article 358), IMC (intermediate, Article 342), and RMC (heaviest, Article 344). Rigid nonmetallic is PVC (Article 352). Flexible types are ENT (nonmetallic tubing, Article 362), FMC (flexible metal, Article 348), LFMC (liquidtight flexible metal, Article 350), and LFNC (liquidtight flexible nonmetallic, Article 356). Each has its own NEC article that governs where and how it may be used.

Which conduit holds the most wires for its size?

Of the rigid types, the ranking depends on trade size. Through 2 inch, IMC has the largest internal area, so it holds the most conductors, followed by RMC, then EMT, with Schedule 40 PVC smaller and Schedule 80 PVC smallest because its thicker wall shrinks the inside. From 2-1/2 inch and larger, the order flips: EMT becomes roomiest, then IMC, then RMC. At 3/4 inch, IMC holds 17 #12 THHN versus 12 for Schedule 80 PVC, five more. The full matrix on this page shows every trade size at the NEC 40 percent fill limit.

What is the difference between EMT, IMC, and RMC?

All three are steel, but the wall thickness and how you join them differ. EMT is thin-wall and uses set-screw or compression fittings, no threads, and is bent with a hand bender. IMC and RMC are threaded rigid conduit: IMC has a thinner wall than RMC, so it is lighter, cheaper, and roomier inside, while RMC is the heaviest and most robust. EMT serves dry exposed runs; IMC and RMC are used where physical protection or a hazardous-location rating is required, with IMC the lighter of the two.

Which conduit is used for underground and wet locations?

PVC (Schedule 40 for direct burial, Schedule 80 where physical damage is a concern) is an underground and wet-location choice because it does not corrode. RMC and IMC are also permitted underground and outdoors, where extra strength is needed, with corrosion protection. The 2023 NEC also permits EMT for direct burial with fittings identified for the purpose and proper corrosion protection, though PVC and rigid metal remain the practical choices underground. For flexible connections in wet areas, use LFMC or LFNC, the liquidtight types. Always follow the NEC 300.5 burial depths for the wiring method you choose.


Related Tools

Pick the type, then run the fill.

Once you know which conduit the job calls for, the fill calculator gives the exact conductor count for any size and mix, per NEC Chapter 9.